Instructions
EN
59
14
(a)
(b)
(c)
(d)
(e) (f) (g) (i)(h)
15
(a)
(b)
(c)
(d)
(e) (f) (g) (i)(h)
Electrical connection of the tubular motor (Figure
n
)
Legend
(a) = set button (11)
(b/d) = socket box
(c) = mains 230 V/50 Hz
Pin assignment
(e) = PE green / yellow
(f) = N blue
(g) = L black
(h) = external switch white/grey (is not connected)
(i) = not assigned brown (is not connected)
IMPORTANT
◆ If the “external switch” (h) lead is not used, then it must be connected to the
neutral conductor (f),(see fig. n).
◆ If the motor is connected in accordance with figure n, then it can only be controlled
via the KNX bus.
Control with a 1-pole switch (closer) (Figure
o
)
Legend
(a) = set button (11)
(b) = 1-pole switch
(c) = mains 230 V/50 Hz
(d) = socket box
Pin assignment
(e) = PE green / yellow
(f) = N blue
(g) = L black
(h) = external switch white/grey *
(i) = not assigned brown
* maximum cable length between tubular motor and external switch = 10 m
The X-line tubular motor can be controlled locally and independently of the KNX bus by
means of connecting a 1-pole switch (closer) to the “external switch” conductor.
In doing so, the switching sequence is as follows:
OPEN/STOP/CLOSE/STOP, and so on.
IMPORTANT
◆ If the “external switch” (h) lead is not used, then it must be connected to the
neutral conductor (f), (see fig. n).