Technical data
76
CTC EcoZenith i550 Pro
For the property owner
9.5.4.4 Quick start Compressor
The delay normally prevents compressor start earlier
than 10 min. after compressor stop. The delay is also
activated in the event of a power failure, or the first time
after production is started. This function speeds up this
process.
Software update via USB
This is only for service engineers. This option can be
used to update the software in the display via USB.
Thesoftware update process is complete when the start
menu appears.
9.5.4.5 Write log to USB
This is only for service engineers. This function can be
used to save logged values to a USB memory stick.
9.5.4.6 Re-installation
This command re-launches the installation sequence.
See the chapter on “First start”.
9.5.4.7 Calibration Sensor
Primary flow VS 1°C (B1) 0.0 (-3.0 to 3.0)
Correction of primary flow sensor B1.
Primary flow VS 2°C (B2) 0.0 (-3.0 to 3.0)
Correction of primary flow sensor B2.
Room temperature 1°C (B11) 0.0 (-3.0 to 3.0)
Correction of room sensor B12.
Room temperature 2°C (B12) 0.0 (-3.0 to 3.0)
Correction of room sensor B12.
Outdoor temperature °C (B15) 0.0 (-3.0 to 3.0)
Correction of outdoor sensor (B15).
Out from solar panels °C (B31) 0.0 (-3.0 to 3.0)
Correction of temperature sensor on solar panels for
outgoing temperature.
Into solar panels °C (B30) 0.0 (-3.0 to 3.0)
Correction of temperature sensor on solar panels for
incoming temperature.
!
NB: The power to the product
must not be interrupted, under any
circumstances, during the update
process.