Technical data
64
CTC EcoZenith i550 Pro
For the property owner
9.5.2.9 Ext Boiler
In this menu settings for the external additional boiler are
made.
Ext boiler diff °C 5 (3...20)
Here you set how much the temperature is allowed to
drop below the stop temperature before the external
boiler starts again.
Minimum temp ext. boiler ° C 30 (10 ... 80)
Start temperature for the external boiler charge pump.
Displayed only when the temperature sensor in the
external boiler is installed and defined.
Delay. Charge pump (min) 0 (0 ... 20)
This function will delay the stop of the charge pump.
The charge pump continues to circulate water during
the set time, after the external boiler has been shut
down. Only applicable for boilers with very small internal
volume of water to prevent overheating.
Tariff ext boiler Off (Off...On)
This indicates whether the product is connected to tariff-
controlled electricity. When the heat pump is turned off
by the grid, the external boiler should activate.
Delay. Stop ext. boiler (min) 0 (0 ... 240)
The stop (shut down) of the external boiler can be
delayed when it’s no longer needed. This is used to
avoid short operating times (risk of corrosion). The boiler
is kept warm during the delay time.
Priority Low (Low...High)
“Low” The external boiler is prioritized after the
immersion heater(s).
“High” The external boiler is prioritized over the electric
heater(s) if both heat sources are defined in the system.
Delay priority low 120(30...240)
Delay of the heat source which has been given “low”
priority. For instance, if the external boiler has the
priority “High”, the immersion heater(s) then get(s) the
priority “Low” and is/are delayed the set number of
minutes before being permitted to engage and assist
in operation. NOTE: Irrespective of the setting, the
immersion heater in the upper tank is used for extra
domestic hot water increase.
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
07-08 00-00 00-00
07-08 00-00 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
03-09 00-00
06-09 00-00
Elec. heater
Upper el.heater(s) kW 9
Lower el.heater kW 9
Lower el.heater °C 50
Delay mixing valve 180
Main fuse A 60
Conversion factor curr. sensors 1:1
Tariff, EL No
Upper tank
Stop temp HP °C 55
Start/stop diff °C 5
Extra DHW stop temp °C 60
Max time upper tank 20
Max time lower tank 40
Min temp °C 45
Add heat upper tank °C 55
Periodic extra DHW, days 14
Max temp diff end DHW °C 3
Stop DHW diff max 3
Run time DHW circ. 4
Time DHW circ 15
Diff start ext DHW buffer 5
Timer DHW circulation
Timer DHW circulation
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Lower tank
Tank max. °C 55
Tank min. °C 25
Diff. tank vs primary °C 0
Start/stop diff tank °C 5
Timer setpoint 50
Timer lower tank
Timer lower tank
Solar panels
dT max solar °C 7
dT min solar °C 3
Min speed pump % 30
Max lower tank °C 85
Max temp brine °C 18
dT max ground °C 60
dT min ground °C 30
Solar test tank min 4
Test frequency min 30
Winter mode Off
Protection collector
Wood boiler
Start at fl ue gas temp °C 100
Ext Boiler
Ext boiler diff °C 5
Minimum temp ext. boiler ° C 30
Delay. Charge pump (min) 0
Delay. Stop ext. boiler (min) 0
Priority Low
Delay priority low 120
External buffer
dT lower ext °C 7
dT start upper °C 7
dT stop upper °C 3
Charge start lower °C 80
dT start lower °C 7
dT stop lower °C 3
dT setpoint lower °C 7
HP charging
Pool
Pool temp °C 22.0
Pool diff. °C 1.0
Pool prio. °C Low
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program Off/Setpoint