Technical data
63
CTC EcoZenith i550 Pro
For the property owner
Anti-freeze No (No/Yes)
As there is a risk of blocks of ice forming in the solar
panels, circulation may be started to reduce the risk of
frost damage.
Anti-freeze temp °C -25 (-30...-7)
Specifies the temperature at which frost protection
should be activated. The menu is displayed when the
Anti-freeze
function has been activated.
9.5.2.8 Wood Boiler
Start at flue gas temp °C 100 (70...250)
This menu is used to define the flue gas temperature
(sensor B8) at which the system is required to enter
wood operation status and the heat pump(s) is required
to be stopped.
Wood operation is activated when the flue gas
temperature exceeds the set value in this menu and
the temperature in the EcoZenith’s lower tank is equal
to or above its reference value (setpoint). When wood
operation is active, the heat pump or additional heat are
not used for heating the EcoZenith. Wood operation is
deactivated when the flue gas temperature drops below
the set value in this menu.
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
07-08 00-00 00-00
07-08 00-00 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
03-09 00-00
06-09 00-00
Elec. heater
Upper el.heater(s) kW 9
Lower el.heater kW 9
Lower el.heater °C 50
Delay mixing valve 180
Main fuse A 60
Conversion factor curr. sensors 1:1
Tariff, EL No
Upper tank
Stop temp HP °C 55
Start/stop diff °C 5
Extra DHW stop temp °C 60
Max time upper tank 20
Max time lower tank 40
Min temp °C 45
Add heat upper tank °C 55
Periodic extra DHW, days 14
Max temp diff end DHW °C 3
Stop DHW diff max 3
Run time DHW circ. 4
Time DHW circ 15
Diff start ext DHW buffer 5
Timer DHW circulation
Timer DHW circulation
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Lower tank
Tank max. °C 55
Tank min. °C 25
Diff. tank vs primary °C 0
Start/stop diff tank °C 5
Timer setpoint 50
Timer lower tank
Timer lower tank
Solar panels
dT max solar °C 7
dT min solar °C 3
Min speed pump % 30
Max lower tank °C 85
Max temp brine °C 18
dT max ground °C 60
dT min ground °C 30
Solar test tank min 4
Test frequency min 30
Winter mode Off
Protection collector
Wood boiler
Start at fl ue gas temp °C 100
Ext Boiler
Ext boiler diff °C 5
Minimum temp ext. boiler ° C 30
Delay. Charge pump (min) 0
Delay. Stop ext. boiler (min) 0
Priority Low
Delay priority low 120
External buffer
dT lower ext °C 7
dT start upper °C 7
dT stop upper °C 3
Charge start lower °C 80
dT start lower °C 7
dT stop lower °C 3
dT setpoint lower °C 7
HP charging
Pool
Pool temp °C 22.0
Pool diff. °C 1.0
Pool prio. °C Low
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program Off/Setpoint