Technical data
59
CTC EcoZenith i550 Pro
For the property owner
9.5.2.4 Upper tank
In the “Upper Tank” menu you make settings which
affect the operation of the upper part of the tank.
Stop temp. HP °C 55 (20 to 60)
At the selected temperature, the heat pump stops
charging the upper tank.
Start/stop diff °C 5 (1 to 7)
Hysteresis before the heat pump starts or stops
charging the upper tank.
Extra DHW stop temp. °C 60 (20 to 62)
This menu is used to specify the setpoint for the heat
pump to charge hot water.
Max time upper tank 20 (5...60)
This is the maximum time spent by the heat pump
charging the upper tank if it is needed in the lower tank.
Max time lower tank 40 (10...120)
This is the maximum time spent by the heat pump
charging the lower tank if it is needed in the upper tank.
Min. temp. °C 45 (35 to 55)
This menu is used to specify the lowest permitted
temperature in the upper tank.
Add heat upper tank °C 55 (45...80)
Stop temperature for additional heat from immersion
heater/external boiler. Used when the EcoZenith is in
additional heating status, when no heat from the heat
pump is available.
Periodic extra DHW, days 14 (0 to 30)
The menu defines the interval for the periodic increase of
the hot water tank (at 65°C to protect against legionella).
Max. temp. diff. interrupted DHW °C 3 (2 to 7)
If there is a heating requirement, hot water charging is
interrupted earlier than the time at which the maximum
temperature has been reached, in order to avoid the
compressor stopping while hot water is swapped for
heating.
Stop DHW diff. max. 3 (2 to 10)
Hot water charging is normally interrupted in the
hot water sensor, but this can also occur in the
condensation temperature which is calculated based
on the heat pump’s internal pressure sensor. The
condensation temperature is significantly increased
during hot water charging. This menu relates to the
value from the maximum permitted condensation
temperature that interrupts hot water charging. If there
is a heating requirement, the system then diverts to
charging the heating system.
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
07-08 00-00 00-00
07-08 00-00 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
03-09 00-00
06-09 00-00
Elec. heater
Upper el.heater(s) kW 9
Lower el.heater kW 9
Lower el.heater °C 50
Delay mixing valve 180
Main fuse A 60
Conversion factor curr. sensors 1:1
Tariff, EL No
Upper tank
Stop temp HP °C 55
Start/stop diff °C 5
Extra DHW stop temp °C 60
Max time upper tank 20
Max time lower tank 40
Min temp °C 45
Add heat upper tank °C 55
Periodic extra DHW, days 14
Max temp diff end DHW °C 3
Stop DHW diff max 3
Run time DHW circ. 4
Time DHW circ 15
Diff start ext DHW buffer 5
Timer DHW circulation
Timer DHW circulation
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Lower tank
Tank max. °C 55
Tank min. °C 25
Diff. tank vs primary °C 0
Start/stop diff tank °C 5
Timer setpoint 50
Timer lower tank
Timer lower tank
Solar panels
dT max solar °C 7
dT min solar °C 3
Min speed pump % 30
Max lower tank °C 85
Max temp brine °C 18
dT max ground °C 60
dT min ground °C 30
Solar test tank min 4
Test frequency min 30
Winter mode Off
Protection collector
Wood boiler
Start at fl ue gas temp °C 100
Ext Boiler
Ext boiler diff °C 5
Minimum temp ext. boiler ° C 30
Delay. Charge pump (min) 0
Delay. Stop ext. boiler (min) 0
Priority Low
Delay priority low 120
External buffer
dT lower ext °C 7
dT start upper °C 7
dT stop upper °C 3
Charge start lower °C 80
dT start lower °C 7
dT stop lower °C 3
dT setpoint lower °C 7
HP charging
Pool
Pool temp °C 22.0
Pool diff. °C 1.0
Pool prio. °C Low
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program Off/Setpoint