Technical data
58
CTC EcoZenith i550 Pro
For the property owner
9.5.2.3 Elec. heater
In the “Elec. heater” menu you can make settings
affecting the operation of the immersion heaters.
El.heater upper kW 9 (0,3...18
Here you select the power that the upper immersion
heaters are allowed to emit.
El.heater lower kW 9 (0,3...9)
Here you select the power that the upper immersion
heaters are allowed to emit
El.heater lower °C 50(30...60)
Setting of temperature for the lower immersion heater.
The lower immersion heater is only allowed to operate
when the heat pump is blocked for some reason.
Delay mixing valve 180(30...240)
This is where the mixing valve delay is set - the period
before it draws energy from the upper part of the
tank. The mixing valve can be blocked so that it never
retrieves energy from the upper part of the tank.
Main fuse A 20 (16...100)
The property’s main fuse size is set here. This setting and
the fitted current sensors ensure the fuses are protected
when using appliances which generate temporary power
peaks, for example, cookers, ovens, engine heaters etc.
The product temporarily reduces power drawn where
this type of equipment is being used.
Conversion factor curr. sensors 1:1 (1...10)
This menu contains the factor the current sensor are to
use. This setting is only performed if the connection has
been installed for a current sensor for higher currents.
Example: User (set) value 2 => 16 A will be 32 A.
Tariff El Off (Off/On)
This indicates whether the product is connected to tariff-
controlled electricity.
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
06-07 00-00 00-00
07-08 00-00 00-00
07-08 00-00 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
03-09 00-00
06-09 00-00
Elec. heater
Upper el.heater(s) kW 9
Lower el.heater kW 9
Lower el.heater °C 50
Delay mixing valve 180
Main fuse A 60
Conversion factor curr. sensors 1:1
Tariff, EL No
Upper tank
Stop temp HP °C 55
Start/stop diff °C 5
Extra DHW stop temp °C 60
Max time upper tank 20
Max time lower tank 40
Min temp °C 45
Add heat upper tank °C 55
Periodic extra DHW, days 14
Max temp diff end DHW °C 3
Stop DHW diff max 3
Run time DHW circ. 4
Time DHW circ 15
Diff start ext DHW buffer 5
Timer DHW circulation
Timer DHW circulation
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Lower tank
Tank max. °C 55
Tank min. °C 25
Diff. tank vs primary °C 0
Start/stop diff tank °C 5
Timer setpoint 50
Timer lower tank
Timer lower tank
Solar panels
dT max solar °C 7
dT min solar °C 3
Min speed pump % 30
Max lower tank °C 85
Max temp brine °C 18
dT max ground °C 60
dT min ground °C 30
Solar test tank min 4
Test frequency min 30
Winter mode Off
Protection collector
Wood boiler
Start at fl ue gas temp °C 100
Ext Boiler
Ext boiler diff °C 5
Minimum temp ext. boiler ° C 30
Delay. Charge pump (min) 0
Delay. Stop ext. boiler (min) 0
Priority Low
Delay priority low 120
External buffer
dT lower ext °C 7
dT start upper °C 7
dT stop upper °C 3
Charge start lower °C 80
dT start lower °C 7
dT stop lower °C 3
dT setpoint lower °C 7
HP charging
Pool
Pool temp °C 22.0
Pool diff. °C 1.0
Pool prio. °C Low
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program Off/Setpoint