Technical data

54
CTC EcoZenith i550 Pro
For the property owner
9.5 Installer
This menu includes four submenus: Time/Language,
Settings, Defined system, and Service.
9.5.1 Time/Language
This is used to set the time, date and language. The
clock saves the settings in the event of a power cut.
Summer/winter time is changed automatically.
Time and date settings
Click on the time symbol.
Press “OK” to highlight the first value and use the
arrows to set the correct value.
Setting the language
Click on the language symbol.
Select the language you want by clicking on the screen.
The language selected is highlighted by a green ring.
Svenska Norsk English Deutsch
Suomi Française Dansk Nederlands
Installer
Time 21:34
Date 2013-06-20
Installer
Installer
Time Language
Installer
Time/Language Settings Defi ned system Service
Settings
Heating circuit 1
Heating circuit 2
Heating circuit 3
Heat pump A1
Heat pump A2
Heat pump A3
Electric heaters
Upper tank
Lower tank
Solar panels
Wood boiler
External boiler
External buffer
Pool
Remote control None
Communication
Save settings
Load settings
Load factory settings
Heat pump A1-A3
Compressor A1 Permitted
Stop at outdoor temp °C -15
Delay between comp. 30
Prio A/W °C 7
Cont. brine pump on No
Compressor stop at brine °C -5
Brine pump on 10 days Off
Tariff, HP Off
Heating circuit 1
Max primary fl ow °C 55’
Min primary fl ow °C Off
Heating off, out °C 18
Heating off, time 120
Inclination °C 50
Adjustment °C 0
Room temp reduced °C -2
Primary fl ow reduced °C -3
Drying period Off
Software display PCB: 20130530 v116
Software HP PCB: 20130503
Svenska Norsk English Deutsch
Suomi Française Dansk Nederlands
Installer
Time 21:34
Date 2013-06-20
Installer
Installer
Time Language
Installer
Time/Language Settings Defi ned system Service
Settings
Heating circuit 1
Heating circuit 2
Heating circuit 3
Heat pump A1
Heat pump A2
Heat pump A3
Electric heaters
Upper tank
Lower tank
Solar panels
Wood boiler
External boiler
External buffer
Pool
Remote control None
Communication
Save settings
Load settings
Load factory settings
Heat pump A1-A3
Compressor A1 Permitted
Stop at outdoor temp °C -15
Delay between comp. 30
Prio A/W °C 7
Cont. brine pump on No
Compressor stop at brine °C -5
Brine pump on 10 days Off
Tariff, HP Off
Heating circuit 1
Max primary fl ow °C 55’
Min primary fl ow °C Off
Heating off, out °C 18
Heating off, time 120
Inclination °C 50
Adjustment °C 0
Room temp reduced °C -2
Primary fl ow reduced °C -3
Drying period Off
Software display PCB: 20130530 v116
Software HP PCB: 20130503
Svenska Norsk English Deutsch
Suomi Française Dansk Nederlands
Installer
Time 21:34
Date 2013-06-20
Installer
Installer
Time Language
Installer
Time/Language Settings Defi ned system Service
Settings
Heating circuit 1
Heating circuit 2
Heating circuit 3
Heat pump A1
Heat pump A2
Heat pump A3
Electric heaters
Upper tank
Lower tank
Solar panels
Wood boiler
External boiler
External buffer
Pool
Remote control None
Communication
Save settings
Load settings
Load factory settings
Heat pump A1-A3
Compressor A1 Permitted
Stop at outdoor temp °C -15
Delay between comp. 30
Prio A/W °C 7
Cont. brine pump on No
Compressor stop at brine °C -5
Brine pump on 10 days Off
Tariff, HP Off
Heating circuit 1
Max primary fl ow °C 55’
Min primary fl ow °C Off
Heating off, out °C 18
Heating off, time 120
Inclination °C 50
Adjustment °C 0
Room temp reduced °C -2
Primary fl ow reduced °C -3
Drying period Off
Software display PCB: 20130530 v116
Software HP PCB: 20130503