Technical data
14
CTC EcoZenith i550 Pro
General Information
2.3.2 Lower tank
In the lower tank the heat pump operates to provide heat to the heating
system. Heat pump operation is of so-called floating condensation type.
However, the lower tank never drops below the set lowest temperature.
Floating condensation operation is where the heat pump heats to the
temperature required by the heating system. This temperature varies
depending on the outdoor temperature and which set inclination and
adjustment (the heat curve for the house) has been chosen. If a room sensor
is installed, this will affect the temperature required in the system. During
spring and autumn, when it is not so cold outside, a lower temperature is
needed for the heating system, but during winter a higher temperature is
needed to maintain the desired indoor temperature.
Savings from a heat pump are directly linked to the COP value. COP means
the output divided by the supplied power. COP 4 therefore means, for
instance, that the heat pump delivers 4 kW and uses 1 kW ( )
The lower the temperature the heat pump needs to deliver, the higher the
COP value obtained from the heat pump, as this will involve the compressor
working to better advantage.
Therefore, the heat pump heats only to the lower tank temperature the
heating system requires. This saves compressor life and maximizes operating
economy. The immersion heater, which is factory installed in the lower tank,
is blocked as long as the heat pump is operating.
The immersion heater is only brought into use if the heat pump is blocked for
any reason.
See also Lower tank Menu in the Detail Description Menus chapter
(Installer/Settings/Lower tank) and the DHW chapter.
4
1
= 4










