Technical data

112
CTC EcoZenith i550 Pro
For the installer
(Y40) Diverting valve external storage tank
230 V 1N~.
2.5 m cable 1.5 mm²
The diverting valve is connected to the following terminal blocks: (Y40)
diverting valve, expansion card X6:
(Y40) Diverting valve, charging/discharging buffer storage
Relay output X6 pole 4
Phase X6 pole 5
Zero: X6 pole 7
Check the function by test running the diverting valve in menu
“Installer/
Service/Function test”
in the control system.
In the “DOWN” position on the function menu, port
should be open (turn
the knob on the motor clockwise, CW). In the “UP” position, port
should
be open (turn the knob on the motor counterclockwise, CCW).
The motor is fitted to the diverting valve by a screw. To unfasten the motor:
remove the knob by pulling it off, unfasten the screw and remove the motor.
To prevent faults, turn the actuator and diverting valve to the starting position
for fitting as shown in the figures. Pull out the knob on the actuator and turn
to the central position.
Port
should be completely open; ports and should be partially open.
Ensure that the groove in the white shaft coupling is in position as shown
in the figure. The diverting valve and actuator can then be fitted together as
shown in the figure, or turned in 90-degree steps relative to each other.
If ports
and have been shifted during the hydraulics connection, the
motor can be reconnected to change its direction of rotation. This is done
using two jumpers inside the motor.
NOTE: the direction of rotation is not changed by shifting the black
and brown cables.
Knob
Actuator
Valve
Groove in
shaft coupling