Specifications
D-10
Group 9: Communication Parameters
Factory
Parameters Explanation Settings Default
Setting
09-00 Communication Address ★ 1 to 254 1
d0: Baud Rate 4800bps
09-01 Transmission Speed ★ d1: Baud Rate 9600bps 1
d2: Baud Rate 19200bps
d3: Baud Rate 38400bps
d0: Warn and keep Operating
09-02 Transmission Fault d1: Warn and RAMP to Stop 0
Treatment ★ d2: Warn and COAST to Stop
d3: No warning and keep Operating
09-03 Overtime Detection
d0: Disable
1
d1: Enable
d0: 7,N,2 (Modbus, ASCII)
d1: 7,E,1 (Modbus, ASCII)
09-04 Communication Protocol ★ d2: 7,O,1 (Modbus, ASCII) 0
d3: 8,N,2 (Modbus, RTU)
d4: 8,E,1 (Modbus, RTU)
d5: 8,O,1 (Modbus, RTU)
APPENDIX D: ZVD Summary of Default Program Codes