Specifications

D-9
Group 8: Special Parameters
Factory
Parameters Explanation Settings Default
Setting
08-00 DC Braking Current Level 0.0 to 100% 0
08-01
DC Braking Time during
Start-Up
0.0 to 60.0 Sec 0.0
08-02
DC Braking Time during
Stopping
0.0 to 60.0 Sec 0.0
08-03 Start-Point for DC Braking 0.00 to 400.00 Hz 0.00
d0: Stop Operation after Momentary
Power Loss
d1: Continues after Momentary Power
08-04 Momentary Power Loss Loss, speed search starts with 0
Master Frequency
d2: Continues after Momentary Power
Loss, speed search starts with
Minimum Output Frequency
08-05
Maximum Allowable
Power Loss Time
0.3 to 5.0 Sec 2.0
08-06 B.B. Time for Speed Search 0.1 to 5.0 Sec 0.5
08-07
Maximum Speed Search
Current Level
30 to 200% 150
08-08 Skip Frequency 1 Upper Bound 0.00 to 400.00 Hz 0.0
08-09 Skip Frequency 1 Lower Bound 0.00 to 400.00 Hz 0.0
08-10 Skip Frequency 2 Upper Bound 0.00 to 400.00 Hz 0.0
08-11 Skip Frequency 2 Lower Bound 0.00 to 400.00 Hz 0.0
08-12 Skip Frequency 3 Upper Bound 0.00 to 400.00 Hz 0.0
08-13 Skip Frequency 3 Lower Bound 0.00 to 400.00 Hz 0.0
08-14 Auto Restart After Fault 0 to 10 0
08-15 Auto Energy Saving
d0: Disable
0
d1: Enable
d0: AVR Function Enable
8-16 AVR Function d1: AVR Function Disable 0
d2: AVR Function Disable for Decel
08-17 Dynamic Braking Voltage 230V: 370V to 430V 380
460V: 740V to 860V 760
d0: Speed Search Starts with Last
08-18 Base-block Speed Trace Frequency Command 0
d1: Speed Search Starts with Minimum
Output Frequency
08-19 Speed Search
d0: Speed Search Disable
0
d1: Speed Search Enable
APPENDIX D: ZVD Summary of Default Program Codes