Specifications

D-8
Group 6: Protection Parameters (Cont.)
Factory
Parameters Explanation Settings Default
Setting
d14: Lv
d15: CF1
06-11 Fourth Most Recent d16: CF2
Fault Record d17: Base Block (B.B.) 0
d18: oL2
d19: CFA
d20: codE
d21: EF1 (External Emergency Stop)
06-12 Over-voltage Stall Level
230V serues: 330V to 410V 390
460V Series: 660V to 820V 780
APPENDIX D: ZVD Summary of Default Program Codes
Group 7: Motor Parameters
Factory
Parameters Explanation Settings Default
Setting
07-00 Motor Rated Current 30 to 120% 100
07-01 Motor No-Load Current 0 to 90% 40
07-02 Torque Compensation 0 to 10 00
07-03 Slip Compensation 0.00 to 3.00. 0.00
07-04 Number of Motor Poles 02 to 10 04
07-05 Motor Auto Detection
d0: Disable
00
d1: Enable
07-06
Motor Line-to-Line
Resistance (R1)
0.00 to 655.35 0.0
07-07 Equivalent Rotor Resistance (R2) 00 to 200% 100
07-08 Motor Rated Slip 0 to 20 Hz 3
07-09 Slip Compensation Limit 0 to 250% 200
07-10
Vector Control Current
d0.0 to d2.0 1.5
Compensation Limit