Specifications

D-3
Group 2: Operation Method Parameters
Factory
Parameters Explanation Settings Default
Setting
d0: Digital keypad
02-00 Source of Frequency d1: 0 to +10V from AVI
Command d2: 4 to 20mA from ACI 00
d3: Potentiometer control (-10 to +10Vdc)
d4: RS-485 communication Interface
d0: Determined by digital keypad
d1: Master Frequency determined by external
terminal, STOP key enable
02-01 Source of Operation d2: Master Frequency determined by external
Command terminal, STOP key disable 00
d3: Master Frequency determined by RS-485
communication interface, STOP key
enable
d4: Master Frequency determined by RS-485
communication interface, STOP key
disable
d0: Ramp Stop; E.F. COAST stop
02-02 Stop Method d1: Coast Stop; E.F. COAST stop 00
d2: Ramp Stop; E.F. RAMP stop
d3: Coast Stop; E.F. RAMP stop
0.75kW to 3.7kW (1 to 5 HP): d1 to d15 15
02-03 PWM Carrier Frequency 5.5kW to 18.5kW (7.5 to 25 HP): d1 to d15 9
22kW to 45kW (30 to 60 HP): d1 to d9 9
55kW to 75kW (75 to 100 HP): d1 to d9 6
02-04 Reverse Operation d0: Enable REV
d1: Disable REV 00
02-05 2-wire/3-wire Operation d0: 2-wire Operation Control Mode (1)
Control Mode Selection d1: 2-wire Operation Control Mode (2) 00
d2: 3-wire Operation Control Mode
2-06 Line Start Lockout
d0: Disable
d1: Enable
0
d0: Decelerate to 0 Hz
02-07 Loss of ACI d1: Stop immediately and display “EF” 0
d2: Continue operation by last frequency
command
APPENDIX D: ZVD Summary of Default Program Codes