Specifications
D-2
APPENDIX D: ZVD Summary of Default Program Codes
Group 1: Basic Parameters
Factory
Parameters Explanation Settings Default
Setting
01-00 Maximum Output Freq.
(Fo,max)
50.0 to 400 Hz 60.0
01-01
Maximum Voltage Frequency
(Base Freq) (Fmax)
0.1 to 400 Hz 60.0
01-02
Maximum Output Voltage 230V series: 0.10V to 255.0V 220
(Vmax) 460V series: 0.10V to 510.0V 440
01-03 Mid-Point Frequency (Fmid) 0.10 to 400 Hz 0.5
01-04 Mid-Point Voltage (Vmid) 230V: 0.1V to 255V 1.7
460V: 0.1V to 510V 3.4
01-05
Minimum Output
Frequency (Fmin)
0.10 to 400.00 Hz 0.50
01-06 Minimum Output Voltage 230V series: 0.1V to 255V 1.7
(Vmin) 460V series: 0.1V to 510V 3.4
01-07 Upper bound of freq. 1 to 110% 100
01-08 Lower bound of freq. 0 to100 % 00
01-09 Accel Time 1 ★ 0.1 to 3600.0 Sec 10.0/60.0
01-10 Decel Time 1 ★ 0.1 to 3600.0 Sec 10.0/60.0
01-11 Accel Time 2 ★ 0.1 to 3600.0 Sec 10.0/60.0
01-12 Decel Time 2 ★ 0.1 to 3600.0 Sec 10.0/60.0
01-13 Jog accel/decel Time ★ 0.1 to 3600.0 Sec 1.0
01-14 Jog Frequency ★ 0.10 Hz to 400.00 Hz 6.00
d0: Linear Accel/Decel
d1: Auto Accel, Linear Decel
01-15 Auto Accel/Decel d2: Linear Accel, Auto Decel 00
d3: Auto Accel/Decel
d4: Linear Accel/Decel Stall Prevention
during deceleration
01-16 S-Curve in Accel 00 to 07 00
01-17 S-Curve in Decel 00 to 07 00
01-18 Accel Time 3 ★ 0.1 to 3600.0 sec 10.0
01-19 Decel Time 3 ★ 0.1 to 3600.0 sec 10.0
01-20 Accel Time 4 ★ 0.1 to 3600.0 sec 10.0
01-21 Decel Time 4 ★ 0.1 to 3600.0 sec 10.0