Specifications

3-3
3.3 Standard Program Code Changes (continued)
Code 07 – 02 (Torque Boost) = 0 (Code 00 - 09 = 2 or 3); = 8 (Code 00 – 09 = 0 or 1)
Code 07 – 04 (Number of Motor Poles) = 4 (Base Speed = 1800 RPM)
Code 07 – 05 (Motor Auto Detection) = 1, then press RUN (To Auto Detect Motor
Resistance); = 0 (Normal)
Code 07 – 06 (Motor Line-to-line Resistance) = ____________ (Auto Detect through or
Measure Using an Ohmmeter)
Code 07 – 10 (Current Limit) = 100 (Software Version 3.12 or later)
Code 10 – 08 (Feedback Signal Detection Time) = 5 (Seconds)
Code 10 – 09 (Transmission Fault Treatment) = 1 (Alarm and RAMP to stop)
Code 10 – 10 (PG Pulse Range) = ____________ (PPR of Feedback Sensor)
Code 10 – 11 (PG Input) = 1 (Single Phase Feedback)
Code 10 – 12 (Proportional Speed Control (P)) = 1.0 (Proportional Setting)
Code 10 – 13 (Integral Speed Control (I)) = .05 (Integral Setting)
Code 10 – 14 (Speed Control Output Frequency Limit) = 10.0 (Hz)
Code 10 – 15 (Feedback Display Factor (1800 rpm @ 60 Hz)) = ____________
Choices: 120 PPR sensor (125), 60 PPR sensor (250), or 30 PPR sensor
(500) (See Code 10 – 10)
NOTE: To reset all codes to factory defaults, set Code 00 – 02 = 10. Reprogram, as
above.