Technical data
W.E.ST.
Elektronik GmbH
Page 19 of 25 PAM-190-P-*-1021 01.12.2014
5.2.6 MIN (Overlap compensation)
5.2.7 MAX (Output limitation)
5.2.8 TRIGGER (Response threshold for the MIN parameter)
Command
Parameters
Unit
Group
MIN X
MAX X
TRIGGER X
x= 0… 6000
x= 2000… 10000
x= 0… 3000
0,01%
0,01%
0,01%
STD
The output signal to the valve is adjusted by means of these commands. With the MAX value the output signal
(the maximum valve control) can be reduced. With the MIN value the overlap (dead zone in the valve) can be
compensated. Via TRIGGER you define to point, when the MIN adjustment is active.
In this way an insensibility area
3
for the input signal is definable.
CAUTION: If the MIN value is adjusted to high, this will have an effect on the
minimum output current (minimum velocity or pressure).
3
This dead zone is necessary, in order that (with noisy input signal) there will be no unwanted MIN triggering.
Input
100%
100%
Output current
MAX
MIN
TRIGGER