Technical data
6 720 611 443 GB (03.11)
Maintenance
35
8.2 Description of servicing operations
The combustion performance must be checked before 
and after any servicing work on the combustion and 
burner components. Refer to section 7.1.
 Check “Last fault stored”:
B Select Service Function .0 (see page 28 “Selecting 
service function”).
There is a list of the fault codes in the Appendix (see 
page 42).
To delete “Last fault stored”:
B Turn temperature control   anti-clockwise as far as 
the stop.
B Press and hold the   button until the display 
shows [].
The last fault stored has now been deleted.
Checking the ionisation current,
Service Function 3.3
B Select Service Function 3.3 (see page 28 “Select-
ing service function”).
If the display shows 2 or 3, the ionisation current is OK. 
If the display shows 0 or 1, the electrode assembly 
(32.1, page 6) must be cleaned or replaced.
Primary Heat exchanger
There is a special accessory kit (no. 840) for cleaning 
the heat exchanger, order no. 7 719 001 996.
B Check control pressure on the air - gas mixer unit at 
max. rated heat output using an electronic manome-
ter.
Fig. 50  
B Remove cleaning access cover (415, page 6) and 
the metal plate below it, if present. Refer to fig. 2.
B Unscrew condensation trap and place suitable con-
tainer underneath. Refer to fig. 51.
B Remove the fan and the burner as described in the 
text headed “Burner” (see page 36).
Fig. 51  
B Loosen any deposits in the heat exchanger from top 
to bottom using the cleaning blade. Refer to fig. 52.
Fig. 52
B Clean the heat exchanger from top to bottom using 
the brush. Refer to fig. 53.
Fig. 53
B Flush the heat exchanger from the top. Refer to 
fig. 54.
i
The heat exchanger should only be 
cleaned if the control pressure is 
4.2 mbar (depression) or less.
6 720 610 332-69.1R
6 720 610 332-72.1R
6 720 610 332-73.1R
6 720 610 332-74.1R










