Technical data

6 720 611 443 GB (03.11)
10
Installation regulations
Condensate analysis, mg/l
Flue system
Elbow - 90 ° Equivalent length 2 m
Bend - 45 ° Equivalent length 1m
Gas supply
2Installation regulations
Gas Safety (Installation & Use) Regulations 1998: All
gas appliances must be installed by a competent per-
son. Failure to install correctly could lead to prosecu-
tion.
The manufacturers notes must not be taken, in any way,
as overriding statutory obligations.
The appliance must be installed in accordance with the
current IEE Wiring Regulations, local Building Regula-
tions, Building Standards (Scotland) (Consolidation),
bye-laws of the local Water Company, Health and
Safety Document 635 (Electricity at Work Regulations
1989) and any other local requirements.
Product Liability regulations indicate that, in certain cir-
cumstances, the installer can be held responsible, not
only for mistakes on his part but also for damage result-
ing from the use of faulty materials. We advise the
installer to avoid any risk by using only quality approved
branded fittings.
The relevant British Standards should be followed i.e.
•BS 6798: Specification for the installation of gas
fired hot water boilers of rated input not exceeding
60kW
•BS 5449: Central Heating for Domestic Premises
•BS 5546: Installation of gas hot water supplies for
domestic purposes
•BS 5440:1: Flues and ventilation for gas appliances
of rated input not exceeding 70 kW (net): Flues
•BS 5440:2: Flues and ventilation for gas appliances
of rated input not exceeding 70 kW (net): Air
Supply
•BS 6891: Installation of low pressure gas pipework
installations up to 28 mm (R1).
•BS 7074:1: Code of practice for domestic heating
and hot water supply
•BS 7671: Requirements for Electrical Installation.
These instructions must be followed.
Ammonium 1.2 Nickel 0.15
Lead 0.01 Mercury 0.0001
Cadmium 0.001 Sulphate 1
Chromium 0.005 Zinc 0.015
Halogenated
hydrocarbons 0.002
Tin 0.01
Hydrocarbons 0.015 Vanadium 0.001
Copper 0.028 pH-value 4.8
Table 3
HORIZONTAL 100 mm – Standard FLUE SYSTEM
Overall Diameter of Duct mm 100
Max.
4m
Flue Terminal / Duct
Assembly Length
mm 600
Extension Duct Length mm 1000
Table 4
HORIZONTAL 125 mm FLUE SYSTEM
Overall Diameter of Duct mm 125 Max.
13 m
(inclu-
ding
turret)
Flue Terminal / Duct Assembly mm 1030
Table 5
VERTICAL 100 mm FLUE SYSTEM
Overall Diameter of Duct mm 100 Excl.
terminal
Max.
5m
Flue Terminal / Duct Assembly mm 1140
Table 6
VERTICAL 125 mm FLUE SYSTEM
Overall Diameter of Duct mm 125 Excl.
terminal
Max.
13.7 m
Flue Terminal / Duct Assembly mm 1365
Table 7
Total length of gas supply pipe
(metres)
Pipe diameter
(mm)
369
Gas discharge rate (m
3
/h)
8.7 5.8 4.6 22
18.0 12.0 9.4 28
Table 8