Technical data
20
Greenstar FS CDi Regular boiler series
horizontal fluing options
Greenstar FS CDi Regular boilers offer a choice of 2 different
sized horizontal RSF flue systems, 100mm diameter and
125mm diameter. The systems have different maximum
lengths. Options 1 to 8 detail the permissible lengths.
Horizontal RSF flue
100mm dia. telescopic flue kit
Comprises:
1 x internal flue connector bend
1 x flue adaptor
1 x flue connector
2 x wall cover plates
530mm (100mm dia.) of flue duct including terminal
Part No. 7 716 191 155
125mm dia. standard flue kit
1 x internal flue connector bend
1 x flue adaptor
1 x flue connector
2 x wall cover plates
965mm (125mm dia.) of flue duct including terminal
Part No. 7 716 191 157
Accessories
Flue diameter 100mm 125mm
Minimum flue length 130mm 350mm
Maximum flue length 4,000mm 13,000mm
The following criteria should be noted when planning the
installation.
•
The concentric flue system must be inclined at 3º
(52mm per metre) from the appliance, to allow
condensate to drain back into the boiler.
•
Because the appliance operates at high efficiency a
white plume of condensation will be emitted from the
terminal. Care must be taken when selecting the flue
terminal position (see pages 18-19).
*The 100mm flue system inclines 2º within the 100mm terminal.
Components Part no. Description
7 716 191 155
60/100 530mm
Horizontal telescopic kit
7 716 191 083 60/100 1m extension
7 716 191 084 60/100 90º bend
7 716 191 085 60/100 45º bend
7 716 191 133 60/100 Short flue extension
7 716 191 164 60/100 Vertical flue adaptor
7 716 191 157 80/125 965mm Horizontal flue kit
7 719 003 666 80/125 1m extension
7 719 003 664 80/125 90º bend
7 719 003 665 80/125 45º bend
7 716 191 165 80/125 Vertical flue adaptor
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Option 1
Extension rear flue horizontal flue assembly
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Maximum
Components required
length (m)
60/100 4 1 up to 4
80/125 13 1 up to 12
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Option 2
Extension rear flue horizontal using a 90º bend
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Maximum
Components required
length (m)
60/100 2.5 1 up to 2 1
80/125 11 1 up to 10 1
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
Min.
120mm
300mm
500mm
Pitched
roof
Flat roof
Min.
120mm
Min.
120mm
Deduct 750mm off the total flue length for every
45º bend used.
Deduct 1,500mm off the total flue length for every
90º bend used.