Technical data
18
Installation on wall
Installation of outside sensor
0.3m0.3m
1.2 - 1.5m
0.6m
119mm
134mm
35mm
1.
2.
3.
Selecting the installation location
Positioning the outside temperature sensor in a suitable location
Installing and commissioning the
FW100 Weather Compensation Controller
Commissioning minimum outside temperature setting
The successful operation of the FW100 Weather
Compensation Controller relies upon the minimum outside
temperature being adjusted to UK standards.
Refer to page 59 of the comprehensive installation and user
instructions supplied with the unit.
Set the minimum outside temperature to UK standards
(as for heat loss calculations), typically -1ºc to -3ºC.
This provides an optimised heat curve to UK conditions.