Instruction manual

ROOM SEALED FLUE OPTIONS
The diagrams (opposite) show the components
used and the maximum flue length (L) for
each flue configuration.
In all cases L is measured from the outside of
the boiler casing.
To achieve the maximum flue length (L), a flue
section will have to be reduced in length.
Only the flue terminal or straight flue
extensions can be reduced in length by
cutting.
The horizontal flue terminal end can be fitted
from the inside or outside of the building.
IMPORTANT:
All horizontal sections must rise away from
the boiler by 52mm per metre (3°) to allow
the condensate to drain back to the boiler.
A - Horizontal terminal
B - Straight flue extension
C - Flue bend 90°
D - Flue bend 45° X 2
E - Vertical terminal
Calculating the flue length:
Measure the total flue length required, noting
that the maximum straight flue length
including
the terminal is:
Horizontal 80/125mm Ø: 4000mm (excluding
120mm of terminal extending outside the building)
Vertical 80/125mm Ø: 6000mm.
Then reduce the total straight flue length for
each extra flue bend (excluding the vertical flue
kit 90° elbow) by:
1000mm for 90°
500mm for 45°
Flue Extension lengths:
Horizontal & Vertical 80/125mm Ø: 1000mm
overall length.
Effective length when engaged into sockets
within the flue run is 950mm.
Flue Terminal lengths:
Horizontal 80/125mm Ø: 720mm
Vertical 80/125mm Ø: 1080mm + cage
* to outside wall.
AC
B
D
E
A
B
C
X 4
A
B
C
X 4
A
B
C
X 4
X 2
E
BX 6
E
BX 4
E
BX 3
X 2
L
L
L
L
L
L
PRE -
INSTALLATION
ROOM SEALED FLUE
OPTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25
8 718 681 134a (08.08)
18
L = 4000mm
L = 4000mm
L = 3000mm
L = 5000mm
L = 6000mm
L = 4000mm