Technical data
** NOTE: The flue gas temperature is measured in the gas sampling hole on the flue outlet plate. The probe should be inserted to a depth of 50mm and angled towards the flue outlet. The temperature measured is not an
absolute flue gas temperature and is for general guidance purposes only!
NOTE: The pump pressure given is for general guidance only as variations in nozzle output can be up to ± 15%. It is, therefore, essential that the air is adjusted to give the correct CO
2
value.
NOTE: The nozzle type used on 28 Sec. Kerosene outputs are nozzles calibrated specifically for use with 28 Sec. Kerosene which gives less variation in nozzle output than the standard 35 Sec. Gas Oil nozzles. However, if a 28
Sec. Kerosene nozzle is not available at servicing or commissioning it is appropriate to install a 35 Sec. Gas Oil nozzle providing the output, spray angle and pattern of the nozzle is the same as the 28 Sec. Kerosene nozzle (e.g.
0.75 80°EH may be replaced with a 0.75 80°H).
4
Fig. 2. Outdoor Pack Principal Dimensions. (All Dimensions are in millimetres)
28 Sec. Kerosene 0.40 60°ES 130 1.11 1.41 180 10 6.0 13.5 46,000 12 41,000
28 Sec. Kerosene 0.50 60°ES 100 1.30 1.64 195 11.5 7.0 15.5 53,000 14 48,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Danesmoor Utility 12/14 Table 2. Electro Oil Inter B9A Burner (See Fig. 29)
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h
28 Sec. Kerosene 0.50 60°ES 110 1.40 1.77 215 10.5 8.5 17 58,000 15 51,000
28 Sec. Kerosene 0.55 80°EH 115 1.59 2.01 225 10.5 8.75 19 65,000 17 58,000
28 Sec. Kerosene 0.60 60°ES 105 1.78 2.25 235 11.5 9.0 21.5 73,000 19 65,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Danesmoor Utility 15/19 and Worcester Bosch 50/70 Table 3. Electro Oil Inter B9B Burner (See Fig. 30)
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h
28 Sec. Kerosene 0.60 80°EH 130 1.87 2.37 190 11.0-11.5 5.5 22.5 77,000 20 68,000
28 Sec. Kerosene 0.75 80°EH 105 2.10 2.66 205 11.5-12.0 6.0 25 86,000 22.5 77,000
28 Sec. Kerosene 0.75 80°EH 130 2.34 2.96 220 12.0-12.5 6.5 28 96,000 25 85,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Danesmoor Utility 20/25 and Worcester Bosch 70/90 Table 4. Electro Oil Inter B11C Burner (See Fig. 31)
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h
28 Sec. Kerosene 0.85 80°EH 110 2.36 2.99 225 11.0-11.5 11 28.5 97,000 26 89,000
28 Sec. Kerosene 0.85 80°EH 130 2.66 3.37 240 11.0-11.5 12 32 109,000 29 99,000
28 Sec. Kerosene 1.00 80°EH 130 2.95 3.74 245 11.5-12.0 16 35.5 121,000 32 109,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Danesmoor Utility 26/32 and Worcester Bosch 90/110 Table 5. Electro Oil Sterling 40 Burner (See Fig. 32)
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h
975
670 760
X= 806 (26/32 and 90/110) X= 811 (on all other models)
Flue terminal
Flue terminal
guard
X
740
238
142
148
68
212
267
798