Technical data

Model AB C D E F G
12/14 370 600 855 780 110 92 56
15/19 (50/70) 370 600 855 780 110 92 56
20/25 (70/90) 370 600 855 780 110 92 56
26/32 (90/110) 520 600 855 775 110 92 56
3
Table 1
3. Technical Data
Fig. 1. Principal Dimensions Of Boiler Fitted Within Outdoor Pack (All Dimensions are in millimetres)
A
CD
G
F
Flue centre
E
B
Front View
Side View
3
Danesmoor Utility MODEL
Worcester Bosch MODEL
PO
IP RATING IP 45 IP 45 IP 45 IP 45
WER SUPPLY
HEATING FLOW
HEATING RETURN
HEIGHT (BOILER)
WIDTH (BOILER)
DEPTH (BOILER)
HEIGHT (OUTDOOR PACK)
WIDTH
DEPTH
FUEL LINE
FLUE REQUIREMENT
HEARTH TEMPERATURE
MAXIMUM STATIC HEAD
BOILER WEIGHT
OUTDOOR WEIGHT
PRIMARY WATER CAPACITY
BURNER
WATER SIDE RESISTANCE
10°C Difference
WATER SIDE RESISTANCE
20°C Difference
EXIT FLUE GAS
MASS FLOW
CONTROL THERMOSTAT
RANGE
CONTROL THERMOSTAT
DIFFERENTIAL
HIGH LIMIT THERMOSTAT
BREAK POINT
MANUAL RESET THERMOSTAT
BREAK POINT
FROST
THERMOSTAT RANGE
12/14 15/19 20/25 26/32
SPECIFICATIONS
230V 50 Hz 230V 50 Hz 230V 50 Hz 230V 50 Hz
1 in. BSP 1 in. BSP 1 in. BSP 1
1
/4 in. BSP
1 in. BSP 1 in. BSP 1 in. BSP 1
1
/4 in. BSP
855 855 855 855
370 370 370 520
600 600 600 600
1
/4 in. BSP
1
/4 in. BSP
1
/4 in. BSP
1
/4 in. BSP
RS Short Silencer 7 716 190 002
20 litres (4.4 gal.) 20 litres (4.4 gal.) 23.5 litres (5.2 gal.) 29.1 litres (6.4 gal.)
94 Kg (207 lbs) 97 Kg (214 lbs) 107 Kg (236 lbs) 138 Kg (304 lbs)
5°C cut in
to
10°C cut out
Electro Oil Electro Oil Electro Oil Electro Oil
Inter B9 A Inter B9 B Inter B11C Sterling 40
7 mbar 8 mbar 18 mbar 35 mbar
3 mbar 6 mbar 12 mbar 19 mbar
24 kg/hr 35 kg/hr 43 kg/hr 57 kg/hr
55°C minimum cut in to 82°C maximum cut out
5°C
100 + 0/ – 6°C
110 + 0/ – 6°C
/ 50/70 70/90 90/110
975
670
760
30m (98 ft. )
Below 100°C
36Kg (79lbs)
(OUTDOOR PACK)
(OUTDOOR PACK)
PACK
SEDBUK RATING* 85.3% 85.5% 85.3% 85.3%
( SEDBUK BAND C )
* The value is used in the UK Government Standard Assesment Procedure (SAP) for energy ratings for dwellings.