The Manuals Library DANESMOOR 12/14, 15/19, 20/25, 26/32, 32/50, 50/70 CONVENTIONAL FLUE AND ROOM SEALED BF FLOOR STANDING OIL-FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS BOILER OUTPUT Hot Water and Central Heating 12/14 MINIMUM 12 kW (41,000 Btu/h) MAXIMUM 14 kW (48,000 Btu/h) 15/19 MINIMUM 15 kW (51,000 Btu/h) MAXIMUM 19 kW (65,000 Btu/h) 20/25 MINIMUM 20 kW (68,000 Btu/h) MAXIMUM 25 kW (85,000 Btu/h) 26/32 MINIMUM 26 kW (89,000 Btu/h) MAXIMUM 32 kW (109,000 Btu/h) 32/50 MINI
Contents 1. 2. 3. 4. 5. 6. 7. 8. Installation Regulations ...........................................Page 2 General Information .................................................Page 2 Technical Data...........................................................Page 3 Siting the Appliance .................................................Page 6 Removal of the Cabinet............................................Page 6 Air Supply..................................................................Page 6 Flue System...
. Technical Data Table 1 SPECIFICATIONS 12/14 15/19 20/25 26/32 32/50 50/70 230/240V 50 Hz 230/240V 50 Hz 230/240V 50 Hz 230/240V 50 Hz 230/240V 50 Hz 230/240V 50 Hz 1 in. BSP 1 in. BSP 1 in. BSP 11/4 in. BSP 11/2 in. BSP 11/2 in. BSP 11/2 in. BSP 11/2 in. BSP 1 in. BSP 1 in. BSP 1 in. BSP 11/4 in.
12/14 Table 2. Electro Oil Inter B9A Burner (See Fig. 21) NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE Fuel 28 Sec. Kerosene 28 Sec. Kerosene Nozzle 0.40 60°ES 0.50 60°ES Pump Pressure (p.s.i.) 135 100 Fuel Flow Rate Kg/h l/h 1.11 1.41 1.30 1.64 Flue Gas Temp. (°C)** 195 210 %CO2 9.5 10.5 Approx. Air Setting 8.0 8.5 Appliance kW 13.5 15.5 Input Btu/hr 46,000 53,000 kW 12 14 Output Btu/hr 41,000 48,000 15/19 Table 3. Electro Oil Inter B9B Burner (See Fig.
26/32 Table 7. Electro Oil Sterling 40 Burner (See Fig. 23) RS Balanced Flue Appliance NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE Fuel 28 Sec. Kerosene 28 Sec. Kerosene 28 Sec. Kerosene Nozzle Pump Pressure (p.s.i.) 0.85 80°EH 0.85 80°EH 1.00 80°EH 110 130 130 Fuel Flow Rate Kg/h l/h 2.36 2.99 2.66 3.37 2.95 3.74 Flue Gas Temp. (°C)** 225 240 245 %CO2 11.0-11.5 11.0-11.5 11.5-12.0 Approx. Air Setting 10 15 20 Appliance Input Output kW Btu/hr kW Btu/hr 28.
from outside the building. Where the air is taken from another room that room must contain an air inlet as described in 6.1. 6.3 There must be sufficient clearance around the appliance to allow proper circulation of ventilation air. The clearances required for installation and servicing will normally be adequate for ventilation. See Section 4.4. ROOM SEALED BALANCED FLUE MODEL ( RS ) 6.4 The appliance does not require a separate vent for combustion air. 6.
Fig. 2. Conventional Flue Appliance (CF/LLD).
Fig. 3. Room Sealed Balanced Flue Appliance (RS).
than 5.1 mm W.g. is experienced a draught stabiliser should be introduced into the flue and adjusted to achieve a flue draught within the specified range. 7. Flue System 7.2 Low Level Discharge A flue system must be provided in accordance with BS5410:Part 1 and the Building Regulations, Part J, Section J2. (See Fig. 5). The conventional flue appliance may be converted to discharge the products of combustion at low level.
Fig. 6. Room Sealed Balanced Flue Terminal Installation. X = 180 mm Maximum X (a) Rear Discharge 4" to 7" Single Skin Wall. For use with non-standard/single skin walls up to 182.mm thick. Where noise emission from the flue terminal is likely to be of concern, it is recommended that the standard 12 in. terminal is used and the appliance stood away from the wall to take up the extra terminal body length. X = 327 mm Maximum X 270 mm FLUE GUARD 340 mm (b) Rear Discharge 7" to 12" Wall.
6. The terminal guard must be evenly spaced about the flue terminal and secured using screws so that the terminal guard can be removed for maintenance to the flue terminal.. Fig. 8. Terminal guard Minimum dimensions. 265 7. In certain weather conditions a terminal may steam and siting where this could cause a nuisance should be avoided. 8. Take care to ensure that combustion products do not enter ventilated roof voids. 280 Terminal guard. See 7.4.5. 280 Fig. 7.
Fig. 9. Oil Pump. 8. Oil Supply A. Danfoss BFP 41. Cartridge filter (See Figs. 9, 10 and 11). 8.1 The oil storage tank must be installed in accordance with BS799 Part 5. The tank should be arranged with a slope of 1 in 24 away from the outlet valve with a sludge cock at its lower end . 8.2 Do not use galvanised steel tanks or pipework for the oil supply system. 8.3 Do not use soldered joints on the oil supply pipework as this could cause a hazard in the case of a fire. 8.
Fig. 10. Oil Supply. Isolating valve Filter Wall Isolating valve Sludge cock Tank raised 1 in 24 (40 mm per metre) Paper element oil filter Non return valve Burner Fire detection element Wall (b) Double pipe system. Isolating valve Isolating valve Non return valve Oil tank Fire valve to BS 799 Part 2 Paper element oil filter Filter Sludge cock Burner H = 0.3 m (1 ft) minimum Fire detection element Fire valve to BS 799 Part 2 H = 3.5 m (11.
Fig. 12. Typical Open Vent Gravity Primary System. Feed and Vent Cistern Heating vent (22mm min.) Primary cold feed (15mm min.) Domestic hot water cylinder S.H. – Minimum static head 1m (3ft) measured from the top surface of the appliance or highest point in the heating system to the water level in the feed and expansion tank S.H. S.H. N.B. A drain cock should be installed at the lowest point of the heating circuit Radiator Pump Boiler Fig. 13.
If an external programmer is to be fitted to the boiler the link plug should be removed from the programmer terminal strip. (See Fig. 15b). The LIVE, NEUTRAL and EARTH wires should be connected to the LIVE, NEUTRAL and EARTH terminals on the main terminal strip and the switched lines connected to terminals 1 and 2. Alternatively, the LIVE, NEUTRAL and EARTH from the programmer may be connected to a separate live supply with the switched lines again connected to terminals 1 and 2.
Fig. 14. Wiring Diagram (Standard). Mains supply 230/240V 50Hz E N L Brown Brown Blue Green/Yellow Blue White Grey 5 Amp. Earth Stud Blue Green/Yellow High limit thermostat Manual reset thermostat Time clock white connecter L N E E N 1 2 3 4 5 6 11 12 13 14 15 7 8 9 10 Post purge black connecter Brown Blue Green/Yellow Brown Orange Green/Yellow Pink Yellow Red Black Brown Brown Grey Black Mains on neon (1) (C) Control thermostat Lockout neon Plug in 1 2 3 4 5 6 connector Post Purge Unit.
Fig. 16. Standard Wiring. NOTE: Remove link 2 to 4 when fitting a room thermostat. Room thermostat 1 3 2 Pump L N E E N 1 2 3 4 5 6 Brown Blue 7 8 9 10 1112 13 14 15 Grey White Brown Blue Green/Yellow Blue Brown ENL Optional Worcester Programmer HEAT SYSTEMS HOT WATER ADVANCE SELECT OFF TWICE ONCE ON PM TUE LOCK SET? OFF TWICE ONCE ON YES HEATING ADVANCE SELECT Burner Socket Fig. 17. Off On No Demand. NOTE: Remove link 1 to 3 and link 2 to 4.
Fig. 18. Honeywell ‘S’ Plan. NOTE: When using a WHS programmer set the switch on the rear of the programmer to ‘P’. Remove link 1 to 3 and link 2 to 4 and make link 3 to 4 N Room thermostat Heating Valve.
Fig. 20. Frost Protection. 2. Remove the blind grommet from the fixed burner surround box and discard. 3. Replace the blind grommet with the open grommet supplied in the plastic bag. 4. Slacken the pipe retaining clip screw located directly below the grommet hole. When using 12mm copper pipe replace the clip with the larger one supplied. 5. Bend a piece of 10mm or 12mm copper tube ( as selected ) to the correct profile to allow the pipe to be fed down the side of the appliance.
control box. Repeat the procedure at least three times or until a steady stream of oil, without air, is exhausted from the bleed port. Re-lock the bleed port. Two Pipe System A two pipe system will automatically vent the air back to the oil tank. Turn on the boiler thermostat and allow the burner to run through to lockout. Wait two minutes and reset the burner control box. Repeat the procedure untill the burner fires and runs in a steady state.
2.20 Add a suitable proprietary corrosion inhibitor such as Fernox or Sentinel. This will inhibit corrosion, protect the circulating pump and valves reducing the possibility of "kettling" noises resulting from deposits of scale and sludge in the boiler. Refer to the product manufacturers instructions for further information. Fig. 21. Electro Oil Inter B9 Burner. (12/14 and 15/19 models) Locking screw Combustion head Combustion Head A Spark gap 2-2.
Fig. 23. Electro Oil Sterling Burner. (26/32 and 32/50 models). Control box Combustion Head A Combustion head Lockout reset button Spark gap 2.5-3.0mm 0mm Transformer Connecting pipe 7.5mm Solenoid valve Draught tube Nozzle Motor Nozzle block Pump Output kW 26-32 32-50 Combustion Head PL 6/7/21.5/10 x 78 mm PL 10/8/10/6/19/10 x 78mm Dimension A 3.5mm 6.0mm Photocell Air adjustment Air adjustment screw (4mm hexagonal screw head) Air control indicator Pressure adjustment screw Fig. 24.
13.1 Hand the users instructions to the user or purchaser for retention and instruct them in the efficient and safe operation of the appliance and the heating/hot water system. (d) On the RS balanced flue model feed the electrical lead back through the grommet seal to give sufficient play to allow withdrawal and inspection of the burner. (e) Slacken the two M6 burner locking screws, using a 5mm allen key, and remove the burner. 2. Clean the fan impeller using the following procedure: 13.
Fig. 25. Location of Boiler Flueway Baffles. (a) 12/14 (c) 20/25 and 26/32 (b) 15/19 Baffle retainer Baffle Baffle Heat shield (d) 32/50 and 50/70 Cap retainer Cap Transit retainer Fig. 26.
M10 nuts and check the fibre glass gasket, it is imperative that this seal is in good condition Replace the seal if necessary (32/50 and 50/70 models only). 3. Remove and check the baffle retainer, where fitted (20/25, 26/32, 32/50 and 50/70 models). See Fig. 25. 4. Remove the baffles, clean and check their condition. Replace any baffles considered to be badly corroded. 5. Remove and check the cap retainer, where fitted (32/50 and 50/70 models only). See Fig. 25d & 26. 6.
15. Short Parts List Part Burner Control 1. Box Photocell Manufacturers Reference Satronic TF830.2 Satronic MZ770 26 Qty 1 1 WHS Part No.
Worn motor bearings. Replace motor. Worn pump. Replace. Pump noise. Air in pump. Noisy operation. Electrode settings incorrect. See installation instructions. Open circuit ignition. Fan out of balance. Replace fan. External controls not operating correctly. Faulty boiler thermostat. Replace if necessary. FAULTY BOILER OPERATION High tension leads faulty. Electrical connections not properly made in control box. IGNITION FAILURE Electrodes broken. Air adjustment fault.
Worcester Heat Systems Limited, Cotswold Way, Warndon, Worcester WR4 9SW. Telephone: (01905) 754624. Fax: (01905) 754619. Technical Helpline: (0990) 266241. www.worcester-bosch.co.uk This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued improvement. All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, 50-70 FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE
EXCELLENCE COMES AS STANDARD Thank you for purchasing a Danesmoor oil-fired central heating boiler. Danesmoor oil boilers are made by Worcester Heat Systems and the strictest quality control standards ever demanded are applied throughout every stage of production. Indeed, Worcester Heat Systems have led the field in innovative boiler design and performance for more than 30 years.
GENERAL INFORMATION To ensure you get the very best from your new Worcester Danesmoor oil boiler, please read these notes and instructions carefully. ELECTRICAL CONNECTION A mains cable should be connected to a double pole isolator with a contact separation of 3 mm on all poles and supplying the appliance and controls only. The mains supply for your Danesmoor boiler is 230/240 volts AC-50Hz. Your boiler must be earthed and protected by a 5-amp fuse.
SERIAL NUMBER Your boiler serial number and model number should always be quoted in any contact with Worcester Heat Systems. This will help identify spare parts and also avoid confusion and delays during any service call-out. You will find these numbers on top of the electrical control box cover plate, and access can be gained by removing the top panel of the boiler casing.
(d) Turn the thermostat control knob to the desired position (see Fig. 2: temperature control). (e) Your boiler will now commence a start sequence, in which a pre-ignition period of approximately 15 seconds is followed by a supply of atomised oil being introduced into the combustion chamber. Ignition then occurs, followed by a post-ignition period of approximately 20 seconds.
MANUAL RESET OVERHEAT THERMOSTAT Sealed system installations require the use of an overheat thermostat which has to be reset by hand. Your boiler is fitted with this thermostat as standard and may be reset by pressing the button shown in Fig. 1. Access is gained by removing the case front panel. If either thermostat persistently cuts out then your boiler requires attention and you should call either your installer or a service engineer.
OPERATING YOUR PROGRAMMER CONTROLS Full instructions on how to install and operate the optional faciamounted programmer are included with the programmer kit. If your boiler operates on gravity feed, the system will only function correctly on heating if the programmer switches on the hot water programme at the same time. To ensure that this is always the case, the programmer is supplied with a gravity system switch on the rear of the unit; this switch must be set to G by your installer.
A call-out charge will be made where: ● ● ● ● The appliance has been installed for over 24 months The appliance has been installed for more than 1 year but less than 2 years and has not had a first annual service by an approved company. OR Our Field Service Engineer finds no fault with the appliance (see note). OR The cause of breakdown is misuse or with other parts of your plumbing/heating system, or with equipment not supplied by Worcester.
MAINTAINING YOUR BOILER’S EFFICIENCY & PERFORMANCE Your new Worcester Danesmoor oil-fired boiler represents a long-term investment in a reliable, high quality product. In order to realise its maximum working life, and to ensure it continues to operate at peak efficiency and performance, it is essential that your boiler receives regular, competent servicing and annual maintenance checks beyond the initial 24 month guarantee period.
SERVICE CENTRES CONTACT NUMBERS: UK Call Centre UK Call Centre Scotland only Tel. Fax. Fax. 08457 256 206 01905 757536 01506 441 687 OPERATING HOURS: Mon - Fri Sat 8.00am to 6.00pm 8.30am to 1.00pm Please contact our UK Call Centre number where our friendly operators will book your call with one of our team of nationwide engineers.
YOUR WORCESTER DANESMOOR GUARANTEE This appliance is guaranteed against faulty materials or workmanship for a period of twenty four calendar months from the date of installation subject to the following conditions and exceptions. 1. That during the currency of this guarantee any components of the unit which are proved to be faulty or defective in manufacture will be exchanged or repaired free of material charges and free of labour charges by Worcester Heat Systems Limited. 2.
Worcester Heat Systems Limited. Cotswold Way, Warndon, Worcester WR4 9SW. Telephone: (01905) 754624. Fax: (01905) 754619. Technical Service Helpline 08705 266241. www.worcester-bosch.co.