Technical data
See Fig. 5 and 6.
7a.1 The system must comply with the requirements of BS 6798
and BS 5449:1.
7a.2 The appliance must not be operated without the system
being full of water, properly vented and pressurised.
7a.3 The pressure relief valve operates at 3bar. The discharge
must be directed away from electrical items or where it might be
a hazard to the user. The pressure relief valve must not be used
for any other purpose.
7a.4 The pressure gauge indicates the system pressure which
must be maintained.
7a.5 The 12 litre expansion vessel is charged to 0.5 bar and is
suitable for a static head of 5m. The pressure can be increased if
the static head is greater than 5m.
7a.6 With an initial system pressure of 0.5 bar, a system capacity
of about 104 litres can be accommodated.Refer to BS 7074 Part 1
for more information.
7a.7 The filling point must be at low level. See Fig. 6.
7a.8 Water loss must be replaced. The connection should be
made in the central heating return as close to the appliance as
possible. See Fig. 6.
7a.9 Any make-up vessel installed must be fitted with a non-
return valve.
7a.10 Repeated venting loses water from the system. It is
essential that this water is replaced and the system pressure
maintained.
7a.11 The pump is set at maximum and must not be adjusted.
7a.12 Connections in the system must resist a pressure of up to
3 bar.
7a.13 Radiator valves must conform to BS 2767(10): 1972.
7a.14 Other valves used should conform to the requirements of
BS 1010.
7a.15 Any system cleaner must be flushed out before an
inhibitor is used.
7a. Sealed System
9
Fig. 6. System filling and make-up.
Top-up Bottle
Non-Return
Valve
Hot Water
Out
Mains
Cold
Water
Lockshield Valve Radiator Valve
Heating Flow
Heating Return
British Standard Stop
Valve.
Fixed spindle type
Water Main
NOTE: A drain cock should
be installed at the lowest
point of the heating circuit and
beneath the appliance.
Appliance
(Refer to
Fig. 1
for appliance
Water Flow
diagram)
Fig. 5. Sealed primary water system.










