Technical data
Refer to Figs. 8, 9, 10 and 11.
10.1 Mains Supply 230V ~ 50Hz 140 watts. External Fuse 3A.
Internal Fuses: 2A Slow (F1), 1A Fast (F2). Both 20mm long.
10.2 Mains cable. PVC insulated 0.75mm (24 x 0.20mm) to
BS 6500 Table 16. The mains cable must be connected into
terminal X1, marked L (brown or red lead), N (blue or black lead),
and the earth cable fixed to the earth bracket at the top of the
electrical box, using a screw and cup washer. Ensure the earth
cable is longer than the other two cables so that it will not be
taut, should the mains cable be pulled.
Feed the mains cable through the top hole at the rear of the
electrical box. Do not omit the cable clamp.
For access to the electrical box, refer to Section 15.
10.3 The appliance must be earthed.
10.4 The wiring between the appliance and the electricity supply
shall comply with current IEE wiring regulations (and any local
regulations which apply) for fixed wiring to a stationary
appliance. NB It must be possible to completely isolate the
appliance with at least 3mm contact separation in both poles.
10.5 If a room thermostat and/or frost thermostat is to be fitted,
refer to Fig.10. These must be suitable for mains voltage
operation.
10.6 A facia mounted twin channel digital programmer is
available as an optional extra. Instructions are suppled with the
programmer kit. Alternatively an external programmer or
timeswitch may be fitted. Refer to Fig.11. This must be suitable
for mains voltage operation.
10.7 SAFETY CHECK
After installation or as a result of an electrical fault, the electrical
system shall be checked for short circuits, fuse failure, incorrect
polarity of connections, earth continuity and resistance to earth.
10. Electrical
12
Fig.8. Wiring diagram.