Operating instructions
1892 1335 - Orion Radio Modem Operating Instructions - v2.9 / Aug 2009 79
Description Set Read Syntax
Base Command Outstation Reply Base Command Outstation Reply
Analogue Ports
Analogue input levels
- - 04 IDS IDD 40
CH
04 IDS IDD 70
mmmm, nnnn, oooo,
pppp CH
Level: bytes mmmm, nnnn, oooo, pppp represent ports 1 to 4
respectively. Value 0 to 1023 represents proportion of full scale
output.
Analogue input range
and alarm conditions
04 IDS IDD 22
cc llll mmmm
nnnn oooo dd ee
ff gg ss CH
04 IDS IDD 52
cc llll mmmm
nnnn oooo dd
ee ff gg ss CH
04 IDS IDD 32
CH
04 IDS IDD 62 cc
llll mmmm nnnn
oooo dd ee ff gg
ss CH
Input range: byte cc bits 0/1, 2/3, 4/5, 6/7 represent ports 1 to 4
respectively.
Value 00 = 0-20mA, 01 = 0-2.5V, 10=0-5V, 11=0-10V
Alarm: bytes llll, mmmm, nnnn, oooo represent ports 1 to 4
respectively. Value 1 - 1023 = alarm level, 0 = no alarm
Dwell time: bytes dd,ee,ff,gg represent ports 1 to 4 respectively: 1 -
255 = no. of 10ms periods, 0 = no dwell time (react immediately)
Direction: byte ss bits 0 to 3 represent ports 1 to 4 respectively: 0 =
if level changes from higher to alarm level or lower (and remains
there for dwell time), 1 = if level changes from lower to alarm level
or higher (and remains there for dwell time)
Analogue output
configuration
04 IDS IDD 35
cc llll mmmm
nnnn oooo dd CH
04 IDS IDD 65
cc llll mmmm
nnnn oooo dd
CH
04 IDS IDD 49
CH
04 IDS IDD 79 cc
llll mmmm nnnn
oooo dd CH
Input range: byte cc bits 0/1, 2/3, 4/5, 6/7 represent ports 1 to 4
respectively.
Value 00 = 0-20mA, 01 = 0-2.5V, 10=0-5V, 11=0-10V
Failsafe level: bytes llll, mmmm, nnnn, oooo represent ports 1 to 4
respectively. Value 0 - 1023.
Failsafe enable: byte dd bits 0 to 3 represent ports 1 to 4
respectively: 0 = no change on failsafe, 1 = level as programmed
on failsafe.
Analogue output levels
(all ports)
04 IDS IDD 23
mmmm nnnn oooo
pppp CH
04 IDS IDD 53
mmmm nnnn oooo
pppp CH
04 IDS IDD 47
CH
04 IDS IDD 77
mmmm nnnn oooo
pppp CH
Level: bytes mmmm, nnnn, oooo, pppp represent ports 1 to 4
respectively. Value 0 to 1023 represents proportion of full scale
output.