Operating instructions

Command Parameters
Description Set Syntax Read
Syntax
Parameter Description Value or
Range
Meaning of Values Default
Value
Dead band and dwell time for ATS304n=l,t ATS304n? n Input number 1 to 4
spontaneous reporting of analogue l Dead band 0 to 255 ADC bits 10
port n t Dwell time 0 to 255 units of 10ms 100
Read Analogue input n ATS301n? n Input number 1 to 4
Returned
value
ADC level 0 to 1023 Proportional to input full scale
Analogue output n h/w configuration ATS305n=m,f,e ATS305n? n Output number 1 to 4
m Output type 1 20mA
2 0 to 2.5V
3 0 to 5V
4 0 to 10V 4= 10V
f Failsafe DAC level 0 to 1023 DAC level, proportional to output
full scale.
e Failsafe enable 0 No change on failsafe 0
1 Level as programmed on failsafe
Analogue output n value ATS306n=a ATS306n? n Output number 1 to 4
a Output value 0 to 1023 ADC level , proportional to output
full scale.
0
Analogue output port for RSSI ATS310=n ATS310? n Analogue output port for 0 Don’t output RSSI anywhere 0
RSSI 1 - 4 Output RSSI on this analogue port
Alarm Summary ATS335? a If an input is in the alarm 0 No alarm
state, the corresponding 1 Analogue input 1 alarm
value is added to a. For 2 Analogue input 2 alarm
example, a=10 indicates 4 Analogue input 3 alarm
an alarm at inputs 2 and 4. 8 Analogue input 4 alarm
d If an input is in the alarm 0 No alarm
state, the corresponding 1 Digital input 1
value is added to d. For 2 Digital input 2
example, d=10 indicates 4 Digital input 3
an alarm at inputs 2 and 4. 8 Digital input 4
l Link (comms) alarm 0 or 1 0 = link OK, 1 = link fail
p PSU alarm 0 or 1 0 = PSU OK, 1 = PSU fail
74 1892 1335 - Orion Radio Modem Operating Instructions - v2.9 / Aug 2009