Operating instructions
1892 1335 - Orion Radio Modem Operating Instructions - v2.9 / Aug 2009 73
Telemetry Input/Output
Command Parameters
Description Set Syntax Read
Syntax
Parameter Description Value or
Range
Meaning of Values Default
Value
Digital input n configuration ATS312n=p,t,d,s ATS312n? n Input number 1 to 4
p Pulse count or digital input 0 or 1 0 = digital input, 1 = pulse counter 0
t Dig alarm enable/ 0 No alarm 0
Count to trigger alarm 1 - 65535 Alarm (digital)(any non-zero value)
Alarm when count reached (pulse)
d Dwell time for digital alarm/
Dwell for spontaneous/ Min
pulse width for count
1 - 255 units of 10ms 1
s Trigger edge for dig alarm/
Trigger edge for count
0 or 1 0 = high to low
1 = low to high
0
Digital input n as PTT (i.e. closure ATS316=n ATS316? n Input to use as PTT 0 No input acts as PTT 0
to 0V turns transmitter on) 1 to 4 Use this input as PTT
Read digital input n level ATS314n? n Input number 1 to 4
Return value Input state 0 or 1 0 = low, 1 = high
Read Pulse Count at input n & reset ATS181n? n Input number 1 to 4
to 0 Returned
value
Pulse count 0 to
65535
Pulses counted at input 1 since the
last reset
Digital output n configuration ATS318n= f,e ATS318n? n Output number 1 to 4
f Failsafe level 0 Output low
1 Output high
e Failsafe enable 0 No change on failsafe 0
1 Level as programmed on failsafe
Digital output n level ATS320n=m ATS320n? n Output number 1 to 4
m Output state 0 or 1 0 = low, 1 = high 1
Analogue input n h/w configuration ATS300n=m ATS300n? n Input number 1 to 4
m Input type 1 20mA
2 0 to 2.5V
3 0 to 5V
4 0 to 10V 4= 10V
Analogue input n Alarm Parameters ATS302n=l,d,s ATS302n? n Input number 1 to 4
l Alarm level 0 No alarm 0
1 to 1023 ADC level for alarm
d Dwell time 0-255 in units of 10ms 0
s Direction 0 or 1 0 = high to low
1 = low to high
0