Operating instructions

54 1892 1335 - Orion Radio Modem Operating Instructions - v2.9 / Aug 2009
Additional Logging Parameters
When Mode L Base station is selected, additional parameters become available on the
Parameters tab.
Figure 23 - ML Base Parameters tab
Poll timer unit (100ms, 1sec or 10sec) is multiplied by the Poll timer time to allow times
from 100ms to 182 hours (over a week). This sets the time interval left between complete
polls of all Outstations. For more detailed information, see pages 23 and 13.
The Number of Outstations is the number which the Base station polls in its sequence. The
poll is contiguous, starting with UnitID=1 and ending with this number as UnitID. Not
applicable to Outstations.
Data Output Port directs the data collected by the Base during the poll either to the normal
User Data port (Port A) to customer equipment, or to the GUI on Port B where the GUI logging
feature (p.57) records it.
v Mode L Outstations always use Port A to collect the data.
The PSU alarm and Alert features which are presented on this tab for other modes are not
used in Mode L Base or Outstation.