Operating instructions

3062449_030924
Commissioning
Programming the following components
1. Wolf boiler control unit COB, Wolf control unit for wall mounted
boilers and MGK standard control unit
Set parameter HG22 (maximum boiler temperature) =
parameter KM03 (maximum header temperature) to + 5 K.
2. BM programming module
Set parameters such as time, day, time programs, etc.
3. Extension modules KM, MM and SM
Match the parameters to the specic requirements.
Start the system again via the system ON/OFF switch (mains "OFF/
ON"). The system is ready to operate after approx. 3 min.
Step 7
Step 8
After the successful commissioning, the number of boilers appears on the BM below the current
time.
Conguration Wolf boiler control unit COB
Parameter HG06 (pump operating mode): Select pump operating
mode 1 in conjunction with Wolf boiler control unit COB.
HG06 = First description see COB control unit manual.
Note: Parameter HG06 must not be changed for Wolf control units
for wall mounted boilers and MGK standard control units.
Step 6