Design Guide

88
|
Wolf Customer Care 800.222.7820
Planning Information
IMPORTANT NOTE: Wolf does not recommend the use
of downdraft ventilation with the grill, steamer or fryer
modules.
Refer to illustrations on the following pages for installation
of integrated modules. For additional induction and electric
modules, refer to the previous cooktop sections.
MULTIPLE COOKTOPS | MODULES
For specic cooktop and module conguration options,
contact Wolf Customer Service at 800-222-7820.
INTEGRATED MODULES
ELECTRICAL
Installation must comply with all applicable electrical codes.
Locate the electrical supply as shown in the illustrations on
the following pages. A separate circuit, servicing only this
appliance is required.
When multiple cooktops or modules are installed side by
side, each must have its own separate electrical supply.
ELECTRICAL REQUIREMENTS
ELECTRIC MODULES
Electrical Supply grounded 3-wire, 240/208 VAC, 60 Hz
Steamer, Fryer 15 amp dedicated circuit
Induction, Electric, Grill 20 amp dedicated circuit
Conduit exible 4'
(1.2 m)
GAS MODULES
Electrical Supply grounded, 120 VAC, 60 Hz
Service 15 amp dedicated circuit
Receptacle 3-prong grounding-type
Power Cord 6'
(1.8 m)