Technical data

AIR SPEED MEASUREMENT INCL. CO
2
-MEASUREMENT | WÖHLER FA 430
ADVANTAGES
· Two measurements in one step: de-
termination of flow rate and evaluation
of the inlet and exhaust air quality via
CO
2
, T, RH
· Easy handling with automatic identifi-
cation of the cone
· Measurement report via IR-transfer
to the Wöhler TD 100 Thermal Fast
Printer
· Wöhler Telescope Handle e.g. for
ceiling vents
· Selectable units: m/s, fpm, m³/h,
CFM, °C, °F, cm², Inch², ppm, %, RH,
WBT, DP
· Determination of the dew point and
wet bulb temperature
· Hold-Function
· Min- / Max-Function
· Backlight LC display
· Simultaneous measurement of wet
bulb temperature and dew point
APPLICATION
· Measurement of air velocity, tempera-
ture, humidity, CO
2
at the air vents
· Integrated measurement of flow rate
· Direct measurement of flow rate at the
air nozzle in combination with a funnel
· Determination of the
inlet and exhaust air quality
Wöhler FA 430 Fan Anemometer
NEW
Wöhler FA 430 Fan Anemometer
incl. CO
2
-Measurement
Scope of delivery:
Wöhler FA 430 Fan Anemometer
4 x AAA batteries
plastic carrying case
Wöhler FA 430 Fan Anemometer Set
with Wöhler FA 4xx measuring funnel set
Scope of delivery:
Wöhler FA 430 Fan Anemometer
4 x AAA batteries
plastic case
Wöhler FA 4xx measuring funnel set with rectangu-
lar and round measuring funnel
in a handy carrying bag; funnels can be clipped
onto the fan anemometer
rectangular funnel: 346 x 346 mm
round funnel: Ø 210 mm
TECHNICAL DATA
Range
Flow velocity.........................0.5 – 30 m/s
Volume flow .........................0 – 99,999 m³/h
Temperature .........................-20.0 °C – 60 °C
Relative humidity ..................0.1% – 99.9%
Dew point ............................-20.0 °C – 59.9 °C
Wet-bulb temperature ........... -20.0 °C – 59.9 °C
CO
2
......................................0 – 9,999 ppm
Resolution
Flow velocity.........................0.1 m/s
Volume flow ........................0.1 (0 – 9,999.9) or
1 (10,000 – 99,999)
Temperature .........................0.1 °C/°F
Relative humidity (RH) ...........0.1 %
Dew point ............................0.1 °C/°F
Wet-bulb temperature .......... 0.1 °C/°F
CO
2
......................................1 ppm
Accuracy
Flow velocity.........................±(1.5 % of reading +
0.3 m/s) for under 20 m/s,
±(3 % of reading + 0.3 m/s)
for above 20 m/s
Temperature .........................± 0.6 °C
Relative humidity .................± 3 % (at 25 °C)),
otherwise ± 5 %
CO
2
......................................± 30 ppm ±5 % of reading
(0 – 5,000 ppm)
CO
2
warm-up time ............. 30 seconds
Operating conditions
(to avoid condensation) ....0 – 50 °C, < 80 % RH
Storage conditions ............-10 °C – 50 °C, < 90 % RH
Power Supply .....................4 micro batteries AAA
Dimensions ........................ 269 x 106 x 51 mm
Fan diameter......................10 cm
Weight (without funnel) ....270 g
E-MAIL: INTERNATIONAL@WOEHLER.DE INTERNET: WWW.WOHLER-INTERNATIONAL.COM