User manual
WT
-
101
0
C2
USER MANUAL
Return Message
ACALARM-ON
5.8.4 Auxiliary Power Down Output Facility via PIN7
In additional to the alarm and text alert on AC fail the system also has a second
permanent +V output continuously supplied from the battery backup via PIN7 output
of the unit which will remain available for the period of AC unavailable.
5.9 “Auto Test” Settings
5.9.1 Setting the Auto Test Report Time Interval
The system has the function of sending the test report to the central station at the
programmable time interval. The time is entered in 24 Hour format.
Text Command:
*DSTM#HH:MM:SS
HH stands for 2 digits value: Hour
MM stands for 2 digits value: Minute
SS stands for 2 digits value: Seconds
Example:
When *DSTM#23:59:00 is applied, it will send the status of the system via
SMS or transmits the Contact-ID to the programmed administrator/central station
number on 11.59pm everyday.
Return Message
DSTM-OK
5.9.2 Enable/Disable the SMS Report of Auto Test
The system has the function of sending auto test report by SMS to the programmable
administrator/central station number. It is possible to enable or disable this function
by sending the following SMS command to the unit.
Text Command:
*DTM?#X
X stands for ON (1) or OFF (0) value
33
WT1010C2 – USER MANUAL – Rev.2.7 – Technical Support : Technical@witura.com
COPYRIGHT ©2008 WITURA CORPORATION SDN BHD