When *ACCA#0 (Default) is applied, it will not dial the administrator/central station
number when AC failed.
To enable this function, you would send *ACCA#1 SMS command to the unit.
Return Message
ACCALL-ON
5.8.2 Enable/Disable the Function of Sending Alert Message when AC Failed
The system has the function to send alert message to the user in the event of power
failure. It is possible to enable or disable this function by sending the following SMS
command to the unit.
Text Command:
*ACMS#X
X stands for ON (1) or OFF (0) value
When *ACMS#1 (Default) is applied, means it will send an alert message when AC
failed.
When *ACMS#0 is applied, means it will not send any alert message when AC failed.
To enable this function, you would send *ACMS#1 SMS command to the unit.
Return Message
ACMESSAGE-ON
5.8.3 Turning the Audible Alarm On/Off for AC failure
The system has the function to sound the connected audible siren when power failure.
This output is available on the connection PIN4 and ground on the main board. To turn
On/Off this function, you can send the following SMS command to the unit.
Text Command:
*ADAL#X
X stands for ON (1) or OFF (0) value
When *ADAL#1 (Default) is applied, means audible alarm will sound when AC failed.
When *ADAL#0 is applied, means audible alarm will not sound when AC failed.
To turn on this function, you would send *ADAL#1 SMS command to the unit.