Note: PSTN Failure Output facility can be used on alarm panel for alert notification
To turn on this function, you can press *31* to proceed.
Example: Setting the unit to generate an Alert Message, call the administrators, generate a pulse
(+V) and sound the audible alarm when AC failed.
Simply input 1111#
Description:
“ME” stands for generation of SMS when AC failed. Default: 0
“AL” stands for sounding the audible alarm when AC failed. Default: 0
“CA1” stands for calling the administrators when AC failed. Default: 0
“CA2” stands for calling the administrators when AC connected. Default: 0
Value: ON (1) or OFF (0)
Auxiliary Power Down Output Facility via PIN7
In additional to the alarm and text alert on AC failure the system also has a second permanent +V
output continuously supplied from the battery backup via PIN7 output of the unit which will remain
available for the period of AC unavailable.
ADC: ME: AL:
CA1: CA2:
ADC: ME: 1 AL: 1
CA1: 1 CA2: 1
ADC: ME: 1 AL: 1
CA1: 1 CA2: 1 OK
Step 11. Setting for AC Failure