User manual

Version: 10/09 Page 4
Specifications
UL 1777 Listed chimney liner (with a 6” (15cm) diameter) up through the block off plate of an existing
masonry chimney, a zero-clearance chimney, or Class A, UL-103 HT, 6” (15cm) diameter chimney
Dimensions (h x w x d) – 60” x 32” x 22” (152cm x 81cm x 56cm)
Firebox Dimensions (h x w x d) – 14” x 24” x 12” (35cm x 60cm x 30cm)
Thermal Output – 20,000 BTU (6 kW); range is 11,100-28,800 BTU
Approximate heating area – 600-1,500ft
2
Minimum stove pressure at above output – 15 Pascals
Efficiency – 75%
Tested EPA emission particulate rate – 6.6 grams/hour
Minimum distances from edge of stove to combustible material – as shown below:
Wall View Corner View
A = Distance to side wall – 12”(30cm)
B = Distance to back wall – 17”(43cm)
C = Corner distance to side walls – 7”(18cm)
D = Connector pipe to side wall – 25”(64cm)
E = Connector pipe to back wall – 18”(46cm)
F = Corner pipe to side walls – 18”(46cm)
G = Distance to furniture – 36”(92cm)
H = Front floor protection (to unprotected combustible floor) – US is 16”(41cm); Canada is
18”(46cm)
I = Side floor protection – US is 8”(20cm) from sides of fuel-loading door; Canada is 8”(20cm)
from the sides of the stove
J = Back floor protection – US is 0”(0cm); Canada is 8”(20cm)
Ceiling to top of stove – 36”(92cm)
Ceiling to connector pipe – 18”(46cm)
Note:
A heat shield or protective wall may be used to reduce clearances if approved by the regulatory authority.
Clearances to noncombustible materials are 2” (5cm), but note that “noncombustible” must be solid
cement or block (not brick or tile over combustible material).