Specifications

Troubleshooting
PROGRAMMING MANUAL 297
Revision 5.0
6.4 TJ1-DRT
6.4.1 System errors
/i
6.4.2 I/O data communication problems
/i
6.5 TJ1-CORT
6.5.1 System errors
/i
COMM LED is off
and BF LED is
flashing
The PROFIBUS configuration is
incorrect, there is no communica-
tion with the master.
Check that you use the cor-
rect GSD file in the master.
Check the configuration and
the parameter data of the
slave.
Check that the network has
been configured to commu-
nicate at the baud rate sup-
ported by the TJ1-PRT.
You have not selected configura-
tion data for the slave.
Check the configuration at the
master.
The TJ1-PRT is defective. Replace the TJ1-PRT.
Indication Problem Solution
No LEDs are on
or flashing
The power is off. Turn the power on.
The TJ1-DRT is defective. Replace the TJ1-DRT.
ERH LED is on Communication failure between
TJ1-MC__ and TJ1-DRT.
Reset the TJ1-MC__. If this does
not help, replace the TJ1-MC__.
ERC LED is on Unit error. The TJ1-DRT is defec-
tive.
Replace the TJ1-DRT.
Indication Problem Solution
Indication Problem Solution
NOK is flashing
and NF LED is off
The DeviceNet master is not com-
municating with the TJ1-DRT.
Configure and start the
DeviceNet master.
NOK off and NF
LED is on
The node address duplication
error.
Check node address.
Network cable error. Check network cables.
Indication Problem Solution
No LEDs are on
or flashing
The power is off. Turn the power on.
The TJ1-CORT is defective. Replace the TJ1-CORT.
ERH LED is on Communication failure between
TJ1-MC__ CPU and TJ1-CORT.
Reset the TJ1-MC__ CPU. If this
does not help, replace the CPU.
ERC LED is on Unit error. The TJ1-CORT is
defective.
Replace the TJ1-CORT.