Specifications

BASIC commands
PROGRAMMING MANUAL 108
Revision 5.0
/i
/i
3.2.162 INVERTER_WRITE
/i
Description INVERTER_READ reads the parameter, speed reference, torque reference
or alarm from the Inverter connected to the system via the MECHATROLINK-
II bus.
There are five INVERTER_READ functions:
0: Reads an Inverter parameter.
1: Reads the Inverter alarm.
2: Reads the speed reference.
3: Reads the torque reference.
4: Reads the Inverter inputs.
To use an Inverter via MECHATROLINK-II you must put the command and
the reference via communication option:
Inverter MV/V7: N3=3; N4=9
Inverter F7/G7: B1-01=3; B1-02=3.
Make you sure that the Inverter firmware supports the MECHATROLINK-II
board.
The command returns 1 if successfully executed and 0 if failed. The result (if
any) is returned in the selected VR.
Arguments module
The number of the TJ1-ML__ that the Inverter is connected to.
station
The MECHATROLINK-II station number of the Inverter.
param_number
The number of the parameter to read. See the Inverter manual.
param_size
The size of the parameter to read, 2 or 4 bytes. Most of the Inverter
parameters are 2 bytes long. See the Inverter manual.
VR
The address in the VR memory of the TJ-MC__ where the read informa-
tion is put. When the function is 4, the result is returned as a bitwise
value. See the table below.
Bit Value Command Description
0 Hex 1 Run forward
1 Hex 2 Run reverse
2 Hex 4 Inverter multifunction Input 3
3 Hex 8 Inverter multifunction Input 4
4 Hex 10 Inverter multifunction Input 5
5 Hex 20 Inverter multifunction Input 6
6 Hex 40 Inverter multifunction Input 7
8 Hex 100 External fault
9 Hex 200 Fault reset
14 Hex 4000 Fault history data clear
15 Hex 8000 External BB command
alarm_number
The number of the alarm to read. See the Inverter manual.
from
The start address of the input to read.
length
The length of the input to read.
Example No example.
See also N/A
Type System command
Syntax INVERTER_WRITE(module, station, 0, param_number, param_size, VR,
mode)
INVERTER_WRITE(module, station, 2, value)
INVERTER_WRITE(module, station, 3, value)
Bit Value Command Description