Installation Manual
6
Type RFB2FC, RFB2-SSFC, RFB4-4DBFC and RFB4-SSFC
preset electrical inserts for use with Type FCPAN floor plate kits
in 2-hour fire rated D900 Series Floor-Ceiling designs
constructed with nominal 2" or 3" deep fluted steel floor units
having nominal 5" wide valleys and crests spaced 12" OC. The
Type RFB2-SSFC and RFB4-SSFC preset electrical inserts are
for use with a minimum 3 1/4" [83mm] thickness of structural
concrete topping. The Type RFB2FC and RFB4-4DBFC preset
electrical inserts are for use with a minimum 4-1/2" [114mm]
thickness of structural concrete topping. The assembled preset
electrical insert with floor plate kit and service activation fitting
will not reduce the 2-hour fire rating of the floor assembly when
installed in accordance with the installation instructions
accompanying the preset electrical insert and when the preset
electrical inserts are spaced minimum 2' [0.61m] OC with not
more than one unit per 4 square feet [0.37m
2
] of floor area in
each span.
1. Installation – Mounted on 2" or 3" [51mm or 76mm] deck. For
use with up to (4) 12 AWG Type THHN power conductors or (48)
23 AWG tele/data conductors per gang
Outlet Boxes and Fittings Classified for Fire Resistance Wiremold/Legrand (R8209)
Step 12 DEVICE PLATES
Use Device Plate supplied. Additional and/or specialty Device Plates are available separately.
For Use on
RFB2-SSFC & RFB2FC
For Use on
RFB4-SSFC
For Use on
RFB4-4DBFC
RFB2DP
RFB2GFI
RFB2B
RFB22AB
RFB2RT
RFB2EXT
RFB-RB-SS
RFB-GFI-SS
RFB-B-SS
RFB-2AB-SS
RFB-2-SSRT
RFB-DR-4DB
RFB-GFI-4DB
RFB-B-4DB
WTB-2-RT
WTB-2-AB