Furniture Feed Style Poke-Thru Device Specifications
* The above maximum copper cross section values are the maximum area of copper to maintain fire classification and are
for each individual power and communication compartments. Do not add values together for any one compartment.
Maximum
Copper Cross
Section
RC7AFFTC Series
Minimum: 3 1/16" [78mm]
Maximum: 3 1/8" [79mm]
1, 1 1/2 & 2 Hours
2 Gangs Two (2) 1/2" & one
(1) 3/4" trade size Screw Plug
Openings
.01536 Sq. in. [9.91 sq. mm]
.004 Sq. in. [2.58 sq. mm]
7" [178mm]
Black, Brass, Aluminum,
Gray
One (1) 3/4" & two (2) 1/2"
trade size Conduit
Minimum: 1/8" [3.2mm]
Maximum: 3/4" [19.1mm]
Minimum: 3" [76mm]
Maximum: 3 1/8" [79mm]
1, 1 1/2 & 2 Hours
2 Gangs Hexagonal Service Head
with one (1) 1/2" trade size
Conduit & five (5) Comm Openings
.05726 Sq. in. [36.94 mm
2
]
.06425 Sq. in. [41.45 mm
2
]
7" [178mm]
Black, Gray
One (1) 3/4" & two (2) 1/2"
trade size
Minimum: 1/8" [3.2mm]
Maximum: 3/4" [19.1mm]
RC9AFFTC Series
3" Diameter Hole
POKE-THRU SERIES
HOLE SIZE
UL FIRE CLASSIFICATION
CAPACITY
POWER*
COMMUNICATIONS*
COVER SIZE
COVER COLORS
CONDUIT/STEM
DIAMETER
FLOOR COVERING
THICKNESS
TopGuard
™
TopGuard
™
UL SCRUBWATER
PROTECTION
Minimum: 3" [76mm]
Maximum: 3 1/8" [79mm]
1, 1 1/2 & 2 Hours
2 Gangs One (1) 1 1/4"
Concentric Screw Plug
.09216 Sq. in. [59.46 mm
2
]
.09216 Sq. in. [59.46 mm
2
]
7" [178mm]
Black, Aluminum,
Gray
One (1) 2"
trade size Conduit
Minimum: 1/8" [3.2mm]
Maximum: 3/4" [19.1mm]
RC9AM2TC Series
TopGuard
™
Die-Cast Die-Cast
COVER CONSTRUCTION
Die-Cast
** The above maximum cable fill area based on Berk-Tek Cat 6 Shield Twisted Pair with an outside diameter of 0.29". Values
above do not account for any fill ratios.
Maximum
Cable Fill
(10) #12 AWG
(7) Cat. 6A/Channel
(11) #12 AWG
(18) Cat. 6A/Channel
POWER**
COMMUNICATIONS**
(18) #12 AWG
(28) Cat. 6A/Channel