Cut Sheet
Catalog No./Item Description/Specifications
RC9AFFTCGY Assembled Furniture
RC9AFFTCBK Feed Unit – Complete
with hexagonal service
head. Service head has one
3/4" threaded conduit hub
and five rubber grommets.
The service head includes
scrub water gasket. Unit
is supplied with one 1 1/4"
trade size conduit stem and
one 1/2" trade size conduit
stem to feed power and
communication services.
The RC9FFTC Series requires
a 3" core hole (3 1/16" [78mm]
actual hole diameter).
UL Listed for tile, carpet,
and wood covered floors.
For complete listing of
RC9FFTC Series accessories,
see current version of Product
Specification Sheet ED1215.
6
Catalog No./Item Description/Specifications
RC9AM2TCGY Furniture Feed Poke-Thru
RC9AM2TCBK Assembled Unit- Complete
RC9AM2TCAL with combination 1 1/4" and 2"
trade size threaded conduit
openings and closure plugs.
Must be used with a conduit
connector (not included) at
the adapter assembly plate
to maintain fire classification.
The RC9AM2TCTC Series
requires a 3" core hole
(3 1/16" [78mm] actual
hole diameter).
UL Listed for tile, carpet,
and wood covered floors.
For complete listing of
RC9AM2TC Series accessories,
see current version of Product
Specification Sheet ED1216.
Chicago Approved Poke-Thru Devices Ordering Information
(Continued)
16 5/8"
[422mm]
Protection from water,
dirt, and debris.
Protection from water,
dirt, and debris.
NOTE:
• Service head is not to be used as a junction box. All
power connections must be made in a junction box
below (not supplied).
• Maximum concrete slab depth for
RC9AM2TC Series = 7.50" [190mm].
• For installations in the City of Chicago, install an EMT
compression fitting (not supplied) to the conduit system and
a junction box suitable for use in environmental air spaces, if
required, (not supplied). Complete installation per NEC and
local codes.
Maximum Allowable Copper Cross-Sectional Area:
RC9AM2TC when communication cables are used
= .09216 sq. in. [59.46mm2].
RC9AM2TC when power cables are used
= .09216 sq. in. [59.46mm2].
NOTE:
• Service head is not to be used as a junction box. All
power connections must be made in a junction box
below (not supplied).
• Maximum concrete slab depth for
RC9AFF Series = 7.50" [190mm].
• For installations in the City of Chicago, install an EMT
compression fitting (not supplied) to the conduit system and
a junction box suitable for use in environmental air spaces, if
required, (not supplied). Complete installation per NEC and
local codes.
Maximum Allowable Copper Cross-Sectional Area:
RC9FFTC Power Compartment only
= .05726 sq. in. [36.94mm
2
].
RC9FFTC Power Compartment only
= .06425 sq. in. [41.45mm
2
].
Catalog Number Explanation
RC9AFFTCGY
RC9 A FF TC GY
Identifies Identifies Identifies Identifies Identifies Color
Poke-Thru Assembled Furniture that Unit is of Cover
Series Unit (A) or Feed Unit Approved for Assembly
Cover (C) Tile and (See below
Carpet Floors for details)
Catalog Number Explanation
RC9AM2TCAL
RC9 AM 2 TC AL
Identifies Identifies Identifies Identifies Identifies Color
Poke-Thru Assembled Furniture that Unit is of Cover
Series Unit (A) or Feed Unit Approved for Assembly
Cover (C) Tile and (See below
Carpet Floors for details)
Poke-Thru Devices on this page are available in some or all of the
following cover color options as indicated by the part numbers:
GY – Gray painted flange with gray nonmetallic cover,
BK – Black painted flange with black nonmetallic cover,
VY – Ivory painted flange with ivory nonmetallic cover,
AL – Brushed Aluminum flange with black nonmetallic cover
BS – Brushed Brass flange with black nonmetallic cover
AA –
Brushed Aluminum flange with aluminum-colored nonmetallic cover
AB – Brushed Brass flange with brass-colored nonmetallic cover
Where applicable, slide covers match the cover color.