Cut Sheet
Catalog No./Item Description/Specifications
RC7AFFTCGY-LJB Flush Furniture Feed
RC7AFFTCBK-LJB Poke Thru Assembly –
RC7AFFTCAL-LJB Complete with one-piece
RC7AFFTCBS-LJB flange and conduit
assembly with one 3/4" trade
size and two 1/2" trade size
conduit adapters and closure
plugs. Colors available in
painted aluminum, black (BK),
gray (GY), forged brush
aluminum (AL), and brass (BS).
The RC7FFTC Series requires
a 3" core hole (3 1/16"
[78mm] actual hole diameter).
UL Listed for tile, carpet,
and wood covered floors.
For complete listing of
RC7FFTC Series accessories,
see current version of Product
Specification Sheet ED1216.
Catalog No./Item Description/Specifications
RC7ATCGY-LJB* Assembled Unit – Prewired
RC7ATCBK-LJB* 20A duplex receptacle can be
RC7ATCAL-LJB* wired as standard duplex or
RC7ATCBS-LJB* isolated ground. Wiremold
RC7ATCVY-LJB* Open System unloaded inserts
RC7ATCAB-LJB* to accept two discrete
keystone connectors from
most manufacturers are
provided.
• Includes 2 Cat 6
TechChoice
™
discrete
keystone connectors.
• Ortronics TracJack bezels.
The RC7 Series requires a 3"
core hole (3 1/16" [78mm]
actual hole diame
ter).
UL Listed for tile, carpet,
and wood covered floors.
For complete listing of RC7
Series accessories, see
current version of Product
Specification Sheet ED1215.
2
Chicago Approved Poke-Thru Devices Ordering Information
9"
[228mm]
7"
[178mm]
7"
[178mm]
9 1/4"
[234mm]
NOTE:
• COM75 Adapter included.
• Maximum concrete slab depth for
RC7-LJB Series = 5.391" [136mm].
• For installations in the City of Chicago, install an EMT
compression fitting (not supplied) to the conduit system and
a junction box suitable for use in environmental air spaces, if
required, (not supplied). Complete installation per NEC and
local codes.
NOTE:
• COM75 Adapter included.
• Maximum concrete slab depth for
RC7AFF-LJB Series = 5.391" [136mm]
• For installations in the City of Chicago, install an EMT
compression fitting (not supplied) to the conduit system and
a junction box suitable for use in environmental air spaces, if
required, (not supplied). Complete installation per NEC and
local codes.
Protection from water,
dirt, and debris.
Protection from water,
dirt, and debris.
Maximum Allowable Copper Cross-Sectional Area:
RC7 Power Compartment only
= .01536 sq. in. [9.91mm
2
].
RC7 Each Communication Compartment only
=
.0040 sq. in. [2.58mm
2
].
Maximum Allowable Copper Cross-Sectional Area:
RC7FFTC Power Compartment only
= .05214 sq. in. [33.64mm
2
].
RC7FFTC Each Communication Compartment only
= .0500 sq. in. [32.260mm
2
].
Poke-Thru Devices on this page are available in some or all of the
following cover color options as indicated by the part numbers:
GY – Gray painted flange with gray nonmetallic cover,
BK – Black painted flange with black nonmetallic cover,
VY – Ivory painted flange with ivory nonmetallic cover,
AL – Brushed Aluminum flange with black nonmetallic cover
BS – Brushed Brass flange with black nonmetallic cover
AA –
Brushed Aluminum flange with aluminum-colored nonmetallic cover
AB – Brushed Brass flange with brass-colored nonmetallic cover
Where applicable, slide covers match the cover color.
Catalog Number Explanation
RC7ATCAL-LJB
RC7 A TC AL LJB
Identifies Identifies Identifies Identifies Color Identifies
Poke-Thru Assembled that Unit is of Cover Junction Box
Series Unit (A) or Approved for Assembly (Not Included)
Cover (C) Tile and (See below
Carpet Floors for details)
Catalog Number Explanation
RC7AFFTCAL-LJB
RC7 A FF TC AL LJB
Identifies Identifies Identifies Identifies Identifies Identifies
Poke-Thru Assembled that Unit is that Unit is Color of Cover Junction
Series Unit (A) or Furniture Approved for Assembly Box (Not
Cover (C) Feed Style Tile & Carpet (See below included)
Floors for details)