Installation Manual
3
Step 4 Push Poke-Thru into floor.
Step 3 Place appropriate gasket around
poke thru and slide under flange.
Use flat foam gasket for surface
t
ile applications or use round
neoprene gasket for carpet
applications. For the flush tile
applications no gasket is needed.
Step 2 If circuit is connected to an isolated
ground, apply IG icon on receptacle
plate as shown.
Step 5 Installation complete.
F
or Carpet or Surface Mounted Tile Installation
For Flush Tile Installation (Start with Steps 1 & 2 on previous page.)
Step 3 Place shims around bottom of flange to
match thickness of tile. Flange is 1/8"
thick. (2) 1/8" shims and (2) 1/16" shims
are provided. Push Poke-Thru into floor.
Step 4 Use grout and/or silicone caulk
between edges of flange and tile.
NOTE: If more shims are required, use Cat. No 8TS.
NOTE: The orange triangle shall only be placed
on devices that are wired for isolated
ground. See NEC 250-146(d).