Installation Manual

2
C
ONVENTIONAL WIRING SCHEMATIC ISOLATED GROUND WIRING SCHEMATIC
BLACK or HOT BLACK BLACK or HOT BLACK
From branch circuit from Poke-Thru receptacle From branch circuit from Poke-Thru receptacle
W
HITE or NEUTRAL WHITE WHITE or NEUTRAL WHITE
From branch circuit from Poke-Thru receptacle From branch circuit from Poke-Thru receptacle
GREEN or GROUND GREEN ISOLATED GROUND GREEN
F
rom branch circuit from Poke-Thru receptacle From branch circuit from Poke-Thru receptacle
System Ground
GREEN or GROUND
GREEN (jumper wire)
F
rom branch circuit from Poke-Thru
System Ground junction box
Step 1 Attach data and AV plates and wire power and data devices (Can be completed above floor).
Refer to wiring schematic below for power wiring options.
INSTALLING COMPLETE ASSEMBLY
Catalog Nos. 8ATCP, 8ATP
WARNING: Ground wire from junction box must be connected to system ground.
CAUTION: Receptacle mounting means not grounded. Grounding wire connection required. For isolated ground
wiring, connect ground leads to a separate isolated grounding conductor. See NEC 250-146(d).
If necessary remove Feed Plates to pull communications wires through Poke-Thru device.
Replace Feed Plates when finished pulling wires.
Catalog Nos. 8ATCP, 8ATP
CAUTION: To maintain fire classification, Feed Plates must be installed.
GREEN (jumper wire)
from Poke-Thru
junction box
Circuit A Wiring
C
ircuit B Wiring
C
ONVENTIONAL WIRING SCHEMATIC ISOLATED GROUND WIRING SCHEMATIC
BLACK or HOT RED BLACK or HOT RED
From branch circuit from Poke-Thru receptacle From branch circuit from Poke-Thru receptacle
W
HITE or NEUTRAL WHITE W/ BLUE STRIPE WHITE or NEUTRAL WHITE W/ BLUE STRIPE
From branch circuit from Poke-Thru receptacle From branch circuit from Poke-Thru receptacle
GREEN or GROUND GREEN W/ YELLOW STRIPE ISOLATED GROUND GREEN W/ YELLOW STRIPE
F
rom branch circuit from Poke-Thru receptacle From branch circuit from Poke-Thru receptacle
System Ground
GREEN or GROUND
GREEN (jumper wire)
F
rom branch circuit from Poke-Thru
System Ground junction box
GREEN (jumper wire)
from Poke-Thru
junction box