Operating instructions

15 Technical Data WirelessHART Fieldgate SWG70
86 Endress+Hauser
15 Technical Data
15.1 Input
Wireless interface WirelessHART communication interface
Physical layer IEEE 802.15.4; 2006
Transmission rate Nominal 250 kBits/s
Operating frequency 2.4 GHz (ISM band)
Transmission range Under reference conditions: Outdoor 250 m, indoor 50 m
RF power level Configurable 0 dBm or 10 dBm, depending upon natioinal regulations
Input variables Process variables according to HART standard sent in burst mode by devices in network
Additional functions Security mode for join key and network ID download (enabled by DIP switch)
• Buffering of process values for acquisition by host application
15.2 Output
15.2.1 Ethernet (100 BASE-T/100 BASE TX)
Protocol Configurable for HART IP and MODBUS TCP communication
Transmission rate 100 Mbit/s (max. cable length 100 m at 25 °C ambient temperature)
Type of protection None
Galvanic isolation Fully isolated from all other circuits
Maximum bus length 100 m (110 yds) depending upon cable
Connection facilities • 7-port terminal block
• Screw terminals: 0.2 mm
2
to 4 mm
2
for solid wire, 0.2 mm
2
to 2.5 mm
2
for stranded wires
15.2.2 RS-485 serial interface
Protocol Configurable for HART Version 7.0 or MODBUS RTU communication
Transmission rate Hardware or software configurable between 1200 Bit/s to 115200 Bit/s
Type of protection None
Galvanic isolation Fully isolated from all other circuits
Maximum bus length 1200 m (1230 yds), depending upon cable and transmission rate
Terminal resistor Integrated, settable by hardware (DIP-switch) or software
Connection facilities Two 3-port terminal blocks, allowing series connection of several Fieldgates
• Screw terminals: 0.2 mm
2
to 4 mm
2
for solid wire, 0.2 mm
2
to 2.5 mm
2
for stranded wires