Operating instructions

WirelessHART Fieldgate SWG70 14 Trouble-Shooting
Endress+Hauser 85
14.2.3 Wireless Communication Faults
Problem Cause/Remedy
1 Fieldgate SWG70 cannot find a WirelessHART device
in the network
The device has not yet joined the network
The joining process may take a while
Check the join status in the gateway's Instrument List
Alternatively, check the wireless communication
parameters (join status) of the device via a HART
modem connected to the device
The device carries the wrong network ID and/or the
wrong join key
Check the wireless communication parameters of the
device via a HART modem connected to the device.
The device and the gateway must have the same
network ID and join key.
2 The wireless connection to a WirelessHART device is
poor and disappears from time to time
There are not enough neighboring WirelessHART devices
within the device's antenna range
Check the number of neighbors
Diagnosis > Wireless Communication
There should beat least 2 neighbors
Signal too weak
Check the signal level of next neighbour in the device
diagnosis - this must be larger than -80 dBm if the
network is to work properly
Improve signal strength by repositioning the antenna
or adding adapters as repeaters
Walls or other static/moving objects block the radio
signals, or the antenna is not aligned vertically
Reposition the gateway or use an external antenna.
3 The Network ID and the Join Key cannot be
downloaded to Fieldgate SWG70
The security DIP Switch 8 is OFF
Set DIP Switch 8 to ON (if Gateway installed in Ex-
Zone 2, switch off power before doing this)
If you want to continue using security mode, set the
DIP Switch 8 to OFF, after the Network ID and Join
Key have been downloaded
4 A device appears with a yellow icon in the instrument
list
Either the device or the communication is faulty
5 A device appears with a red icon in the instrument list The device is faulty
The network was switched off for sometime, but the
device has continued transmitting.
The device has gone into prolonged sleep mode
Either wait until the device reappears (waiting time
depends on how long the network was not present) or
press the adapter’s push button for 5 seconds to force
joining
6 A device is present in the network, but bursting is
interrupted
The field device is being configured locally by a modem
When a modem is communicating with the adapter, it
is impossible to measure the loop current and bursting
is disabled
Bursting will restart when the modem is disconnected