Operating instructions
WirelessHART Fieldgate SWG70 10 Engineering
Endress+Hauser 71
Manual entry of an
Input Register mapping
table
1 Click on the Table tab to open the Table dialogue:
2 Select a device from the drop-down menu that appears when the Long Tag field is clicked
3 Enter an offset value in the Register field.
– Offset value >1: For the first device entered, an extra field will be added for the registers
0 to e.g. 200 that lie before the entered value
– The line turns red indication mission entries and remains so until all entries are made
– For subsequent entries, missing entries are outlined in red.
4 Select the value you want to read for the device in the Value column
– If you select CMD 48 Device Status enter a response byte as well
– For more information, see CMD48 Read Additional Status Information, Chapter A.3.3
5 Repeat Steps 2, 4 and 5 for all other devices
6 If required, manually edit the mapping table by deleting unwanted entries with the delete
button
7 After the mapping table is complete, click Apply to store the it in Fieldgate SWG70.
Import and Export of
mapping tables
The export/import functionality can be useful if you want to create the mapping table using a
spreadsheet program, or if you want to import a backup of an existing mapping table.
1 To export the current mapping table to a CSV file, click Export.
2 To load the mapping table from a CSV file, click Import
– Click Apply to store the imported mapping table in Fieldgate SWG70
3 To reload the mapping table currently used by Fieldgate SWG70, click Refresh