Operating instructions

WirelessHART Fieldgate SWG70 10 Engineering
Endress+Hauser 69
Input Register parameters
Parameter Meaning Example Default
Table
Register Defines the start register for the HART device values
For Input Register the first value is normally 30000; some
systems work only with Holding Registers starting at 40000
The intial value can be overwritten only after a device has been
selected in the Long Tag drop-down menu
Subsequent start registers are automatically generated
13 1
End Register End register for HART device values (generated automatically) 14 65531
Long Tag Click to open a drop-down list of connected network devices
IO-Card Identifier of fieldgate card used by the device
Channel Identifier of card channel used by the device
Value Click to open a drop-down list of values for the selected device
Delete button Depending upon position, deletes the table or the table line
Generate
Start Register Defines the start register for the first HART device
For Input Registers this is normally 1, depending on the Modbus
system in use
13 1
Generation Order Order in which the devices are mapped to the Modbus registers.
Index: According to the index number, see Instrument List,
Chapter 10.1, for example
Alphabetical: In alphabetical order according to the Long Tag
Alphabetical (sub-device): In alphabetical order according to the
Long Tag of the sub-device.
IO card & channel: According to the IO card & channel number
of the wireless device.
IO card & channel (sub-device): According to the IO card &
channel number of the sub-device.
Value Click to open a drop-down list of values for the selected device
Delete button Depending upon position, deletes the table or the table line
Default Settings Adds all HART Command 3 values to the value list, see Appendix A
Generate Writes mapping table to table in Table tab
Delete all mappings Checked: Overwrites any table already in Table tab
Unchecked: Adds any new devices found to existing table
Controls
Import Imports a mapping table in CSV format
Export Exports the current mapping table in CSV format
Refresh Loads the mapping table currently stored in Fieldgate SWG70