Operating instructions

WirelessHART Fieldgate SWG70 10 Engineering
Endress+Hauser 65
Input Status parameters
Parameter Meaning Example Default
Table
Register Defines the start register for the Digital I/O device values
For Input Status the first value is normally 1
The initial value can be overwritten only after a device has been
selected in the Long Tag drop-down menu
Subsequent start registers are automatically generated
11
End Register End register for Digital I/O device values (generated automatically) 8 65536
Long Tag Click to open a drop-down list of connected network devices
IO-Card Identifier of fieldgate card used by the device
Channel Identifier of card channel used by the device
Value Click to open a drop-down list of values for the selected device
Least Significant Byte: maps bits 0 - 7 of a UINT16 to one register
each
Most Significant Byte: maps bits 8 - 15 of a UINT16 to one
register each
––
Value field Enter an appropriate value into the field which opens when a value
is selected
0: the 1st discrete value of a device is mapped
...
255: the 256th discrete value of a device is mapped
00
Delete button Depending upon position, deletes the table or the table line
Generate
Start Register Defines the start register for the first Digital I/O device
For Input Status this is normally 1
11
Generation Order Order in which the devices are mapped to the Modbus registers.
Index: According to the index number, see Instrument List,
Chapter 10.1, for example
Alphabetical: In alphabetical order according to the Long Tag
Alphabetical (sub-device): In alphabetical order according to the
Long Tag of the sub-device.
IO card & channel: According to the IO card & channel number
of the wireless device.
IO card & channel (sub-device): According to the IO card &
channel number of the sub-device.
––
Value Click to open a drop-down list of values for the selected device
Least Significant Byte: maps bits 0 - 7 of a UINT16 to one register
each
Most Significant Byte: maps bits 8 - 15 of a UINT16 to one
register each
––
Value field Enter an appropriate value into the field which opens when a value
is selected
0: the 1st discrete value of a device is mapped
...
255: the 256th discrete value of a device is mapped
00
Delete button Depending upon position, deletes the table or the table line
Generate Writes mapping table to table in Table tab
Delete all mappings Checked: Overwrites any table already in Table tab
Unchecked: Adds any new devices found to existing table
––
Controls
Import Imports a mapping table in CSV format
Export Exports the current mapping table in CSV format
Refresh Loads the mapping table currently stored in Fieldgate SWG70
Apply Stores the current mapping table to Fieldgate SWG70